Power Cable Connect - KStar YMK3300-200k Operation Manual

Table of Contents

Advertisement

500k
600k
CAUTION!
Protective earth cable: Connect each cabinet to the main ground system. For
Grounding connection, follow the shortest route possible.
WARNING!
FAILURE TO FOLLOW ADEQUATE EARTHING PROCEDURES MAY
RESULT IN ELECTROMAGNETIC INTERFERENCE OR IN HAZARDS
INVOLVING ELECTRIC SHOCK AND FIRE

3.7 Power cable connect

Before equipment has been installed, must comfirm the input source type, common input or Split
input, if the input source is dual input, must remove the copper bar that connected bypass and mains.
Choose appropriate power cable. (Refer to the table above) and pay attention to the
diameter of the connection terminal of the cable that should be greater than or equal to that of
the connection poles;
Mains input circuit breaker
Bypass input circuit breaker
Output circuit breaker
Mains input circuit breaker
Bypass input circuit breaker
Output circuit breaker
24
1000A 3P
800A 3P
800A 3P
1250A 3P
1000A 3P
1000A 3P