Digital Input:
s.
Analog Input: Humidity Sensor:
t.
Analog Input: Return Air Sensor:
u. Analog Input: Static Air Pressure:
v.
Analog Input: Discharge Air Pressure:
w. Analog Input: Chilled Water Sensor:
x.
Analog Input: Outside Air Temp:
y.
Optional Sensor #1: Choose Name:
dap4 Settings for Ultra Units
Manual Override Channel:
Action:
Delay:
Status:
Enable:
Channel:
Normal:
Minimum:
Maximum:
Offset:
Value:
Enable:
Channel:
High Res.:
Offset:
Value:
Enable:
Channel:
Normal:
Min 1/1000" H2O:
Max 1/1000" H2O:
Offset:
Air Press:
Enable:
Channel:
High Res.:
Offset:
Value:
Enable:
Channel:
High Res.:
Offset:
Value:
Enable:
Channel:
Normal:
Offset:
Value:
Enable:
Channel:
Normal:
Offset:
Value:
94
ID18 (Default)
Closed (Default)
5s (Default)
Open
Info Only Based on Sw State
On (Default)
U01 (Default)
4-20mA (Default)
0.0 (Default)
100.0 (Default)
0.0 (Default)
000.0 (Reading, not a setting)
On (Default)
U04 (Default)
NTC (Default)
0.0 (Default)
000.0 (Reading, not a setting)
Off (Default)
U07 (Default)
0-10VDC (Default)
0 (Default)
5000 (Default)
000 (Default)
0.000" Wtr
(Reading, not a setting)
On (Default)
U09 (Default)
NTC (Default)
0.0F (Default)
0.000F
(Reading, not a setting)
Off (Default)
U10 (Default)
NTC (Default)
0.0F (Default)
0.000F
(Reading, not a setting)
Off (Default)
U05 (Default)
NTC (Default)
0.0F (Default)
0.000F
(Reading, not a setting)
Off (Default)
U02 (Default)
NTC (Default)
0.0F (Default)
0.0F
(Reading, not a setting)
gForce Ultra IOM