Data Aire gForce Ultra Installation, Operation & Maintenance Manual page 89

Hide thumbs Also See for gForce Ultra:
Table of Contents

Advertisement

c.
Variable Compressor 1:
NOTE: When Analog Output Config: Optional Output #2 is changed, these speeds must be
changed proportionally. Example: Max Speed = (6000 RPM / 10) x 9.0 VDC = 5400 RPM
d. Variable Compressor 2:
e. Variable Compressor 3:
f.
Options Installed:
g. Reheat Settings:
dap4 Settings for Ultra Units
Band:
18.0F (Default)
Integration Time:
1000s (Default)
Derivative:
0 (Default)
C1 Offset:
2.0F (Default)
C1 Off Delay:
60s (Default)
Minimum Speed:
1500 RPM
Maximum Speed:
6000 RPM
Delay Modulation:
Not required for a GUXX-
C2 Offset:
GUXX-045XX models –
C1 Boost Time:
Ignore any parameters in
C2 On Delay:
C2 Off Delay:
Oil Boost Delay:
Suction Pr:
Not required for a GUXX-
GUXX-045XX models –
Cut Out SP:
Ignore any parameters in
Differential:
Delay C1 Start:
Maximum PD Time:
SH PD Cut-In:
Electronic Valve:
pCOe (Default)
Expansion Module:
No (Default)
Power Meter:
AC Pwr Loss Cap:
No (Default)
Yes (Air-cooled systems)
Enable Pump Down:
No (Water/Glycol-cooled systems)
None (Default)
Rack Temp:
Reheat Stages:
None See Job Instructions
Enable Rotation:
Yes (Default)
Lead Reheat:
First (Default)
Dly After CL:
10 min (Default)
Enable SCR Y4:
No (Default)
Band:
1F (Appears if SCR is enabled)
89
22kW
36-45kW
022XX, GUXX-036 or
this menu, they do not
apply.
22kW
36-45kW
022XX, GUXX-036 or
this menu, they do not
apply.
22kW
36-45kW
Sngl
Sngl
gForce Ultra IOM
70, 91, 125kW
60s (Default)
1.0F (Default)
60s (Default)
60s (Default)
60s (Default)
90s (Default)
70, 91, 125kW
XX PSI
(Reading, not a
setting)
80 PSI (Default)
40PSI (Default)
5s (Default)
60S (Default)
30.0 (Default)
70, 91, 125kW
Dual