Data Aire gForce Ultra Installation, Operation & Maintenance Manual page 91

Hide thumbs Also See for gForce Ultra:
Table of Contents

Advertisement

q.
r.
Fan Flow Tuning PID -
5.
Menu K - Alarms & Limits
a. Alarm Setting:
b. Alarm Settings:
c.
Flow Alarms:
d. Return Air Alarms:
e. Opt Temp Alarms:
f.
Humidity Alarms:
g. Freeze Alarm:
h. EEV Alarms:
dap4 Settings for Ultra Units
Number of Fans:
Fan K-Factor:
Minimum Flow:
Maximum Flow:
Set Point:
This screen will display if Display Airflow is selected
Status:
Setpoint:
Integration Time:
Band Per Fan:
Deviation Time:
Current Demand:
Audio Mode:
Pwr-Up:
EVD Alm Shutdown:
Maint Due Msg:
Stdby Alms Active:
Comp Short Cycle:
Floor Water Alarm Action:
Reset Alarm Log:
Alarm Screen Contact:
No Water Flow Action:
Wtr Flow Alm Dly:
Air Flow Dly:
Firestat Setpoint:
Hi Temp Alarm:
Set Point:
Lo Temp Alarm:
Set Point:
Low Disch Temp Alm:
Shut Off Comps:
Set Point:
HI Humidity Alarm:
Set Point:
Lo Humidity Alarm:
Set Point:
Freeze-Stat Alarm:
Shutdown Comps:
Hi Superheat Delay:
91
One
(Default)
348
(Default)
2000 CFM (Default)
32000 CFM (Default)
15000 CFM (Default)
00 CFM
(Reading, not a setting)
15000 CFM
5S
666 CFM
1s
40%
None (Default)
Auto, No Alarm (Default)
Yes (Default)
None (Default)
No (Default)
Yes (Default)
Alarm Only (Default)
No (Default)
No Contact Message (Default)
Alarm Only (Default)
5s (Default)
5s (Default)
150F (Default)
Yes (Default)
80F (Default)
Yes (Default)
60F (Default)
Yes (Default)
No (Default)
45.0F
Yes (Default)
60% (Default)
Yes (Default)
40% (Default)
No (Default)
Yes (Default)
90s (Default)
gForce Ultra IOM