h. Digital Input:
i.
Digital Input:
Humidifier Fault Sw Channel:
j.
Digital Input:
Energy Saver Switch Channel:
k.
Digital Input:
Hi Condensation Sw Channel:
l.
Digital Input: Fan Overload (Fan Fail) Channel:
m. Digital Input:
Opt Alarm #1 Switch Channel:
n. Digital Input:
Opt Alarm #2 Switch Channel:
o. Digital Input:
Opt Alarm #3 Switch Channel:
p. Digital Input: Opt Alarm #4 Switch
q. Digital Input:
Floor Water Switch Channel:
dap4 Settings for Ultra Units
Dirty Filter Switch Channel:
Action:
Delay:
Status:
Action:
Delay:
Status:
Action:
Delay:
Status:
Action:
Delay:
Status:
Action:
Delay:
Status:
Action:
Delay:
Status:
Action:
Delay:
Status:
Action:
Delay:
Status:
Channel:
Action:
Delay:
Status:
Action:
Delay:
Status:
93
ID8 (Default)
Closed (Default)
5s (Default)
Open
Info Only Based on Sw State
ID9 (Default)
Closed (Default)
5s (Default)
Open
Info Only Based on Sw State
ID10 (Default)
Closed (Default)
5s (Default)
Open
Info Only Based on Sw State
ID11 (Default)
Closed (Default)
5s (Default)
Open
Info Only Based on Sw State
ID12 (Default)
Open (When Ziehl-Abegg fans are used)
Closed (When ebm papst fans are used)
5s (Default)
Open
Info Only Based on Sw State
ID13 (Default)
Closed (Default)
5s (Default)
Open
Info Only Based on Sw State
ID14 (Default)
Closed (Default)
5s (Default)
Open
Info Only Based on Sw State
ID15 (Default)
Closed (Default)
5s (Default)
Open
Info Only Based on Sw State
NOTE: Variable Compressor Fault
ID16 (Default)
Closed (Default)
5s (Default)
Open (Default)
ID17 (Default)
Closed (Default)
5s (Default)
Open
Info Only Based on Sw State
gForce Ultra IOM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents