Data Aire gForce Ultra Installation, Operation & Maintenance Manual page 90

Hide thumbs Also See for gForce Ultra:
Table of Contents

Advertisement

h. Water Valve Settings:
CAUTION: NEVER SELECT Chill Wtr Cool or Chill Wtr Reg on Ultra model; otherwise
compressor(s) will not operate.
i.
Humidity Settings:
j.
Humidity Settings 2:
k.
Rack Settings:
l.
Unit Identification:
m. Fan Settings:
n. Fan Range Setting –
Flow, Air Pressure, or BMS Speed is selected
o. Options Installed 2:
p. Diff Air Pressure -
This screen will display if Display Airflow is selected
Fan Air Flow -
This screen will display if Display Airflow is selected
dap4 Settings for Ultra Units
Water Valve:
E-Saver Assist:
Wtr Vlv Action:
Wtr Vlv Voltage:
E/S Startup Time:
E/S Lockout Time:
Switch to DX:
Control:
Humidify:
Auto-Flush:
Dsat Cyc:
Hum Anticipation:
Dehum Mode:
Fan Speed Assist:
Reduce Speed:
Temp Sensors Used:
Model:
Serial Number:
Job Number:
CW mode:
CW speed;
Display Airflow:
Aire-Seal Damper:
DX Mode:
DX Speed:
This screen will display if Mod to Comp, Mod to Rack, BMS Flow, Const
Modulate Min:
Modulate Max:
Condenser Fans:
Evaporator Fans:
Set Point:
Band:
Integration Time:
Fan Speed:
90
None (Default)
Aux Chill Wtr or Engy Svg Cool
Direct (Default)
0-10
0s (Default)
5m (Default)
0 Hrs (Default)
See Job Instructions
Relative Hum (Default)
Compu Non-Mod
Not used (Default),
Not used (Default)
Off (Default)
See Job Instructions
2C In Limit
Off (Default)
20% (Default)
Only appears if fan speed
assist is selected to yes
Optional RackSense module required
0 (Default)
GUXX-022XX-XX
20XX-XXXX-X
4XXXX
Const Speed (Default)
85% (Default)
No (Default)
No (Default)
Mod to Comp
XX% (See Job Instructions)
40% (Default)
XX% (See Job Instructions)
None (Default)
None (Default)
1.000" Wtr (Default)
5.000" Wtr (Default)
50s (Default)
0% (Default)
gForce Ultra IOM