Condensate Drain; Service Access; Thermostat; Power And Control Wiring - Johnson Controls BUQ024 Installation Manual

R-410a 2-5 ton
Hide thumbs Also See for BUQ024:
Table of Contents

Advertisement

527929-BIM-F-0911

Condensate Drain

A condensate trap is recommended to be installed in the
condensate drain. The plumbing must conform to local codes.
Use a sealing compound on male pipe threads. Install the
condensate drain line (3/4" NPTF) to spill into an open drain.
Hand tighten only.

Service Access

Access to all serviceable components is provided at the
following locations:
• Blower compartment access panel
• Electrical/Filter access panel
• Compressor access panel
• Refrigerant connections
Refer to Figures 1 and 3 for location of these access locations
and minimum clearances in Table 4.
This system uses R-410A Refrigerant which operates at
higher pressures than R-22. No other refrigerant may be
used in this system. Gage sets, hoses, refrigerant
containers and recovery systems must be designed to
handle R-410A. If you are unsure, consult the
equipment manufacturer. Failure to use R-410A
compatible servicing equipment may result in property
damage or injury.
8
Wear safety glasses and gloves when handling
refrigerants. Failure to follow this warning can cause
serious personal injury.
Refer to Figure 11 for the R-410A quick reference guide.

Thermostat

The room thermostat should be located on an inside wall
approximately 56" above the floor where it will not be subject to
drafts, sun exposure or heat from electrical fixtures or
appliances. Follow manufacturer's instructions enclosed with
the thermostat for general installation procedure. Six color
coded insulated wires (minimum #18 AWG) should be used to
connect thermostat to unit. See Figure 7.

Power And Control Wiring

Field wiring to the unit must conform to provisions of the current
N.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordinances.
The unit must be electrically grounded in accordance with local
codes or, in their absence, with the N.E.C./C.E.C. Voltage
tolerances which must be maintained at the compressor
terminals during starting and running conditions are indicated
on the unit Rating Plate and Table 5.
The wiring entering the cabinet must be provided with
mechanical strain relief.
A fused disconnect switch should be field provided for the unit.
If any of the wire supplied with the unit must be replaced,
replacement wire must be of the type shown on the wiring
diagram.
Electrical line must be sized properly to carry the load. Each
unit must be wired with a separate branch circuit fed directly
from the meter panel and properly fused.
Refer to Figures 7 and 8 for typical field wiring and to the
appropriate unit wiring diagram for control circuit and power
wiring information.
Johnson Controls Unitary Products

Advertisement

Table of Contents
loading

This manual is also suitable for:

Buq030Buq036Buq042Buq048Buq060

Table of Contents