Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/ VUR09-36 and Chassis Model VSCS09-36 Installation, Operation, and Maintenance Manual Installation Guide Form Number: 145.18-IOM3 (1220) Issue Date: 2020-12-10 Supersedes: 145.18-IOM3 (1019) Johnson Controls...
Page 2
Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
System flushing and cleaning......................40 Flushing the system..........................40 Cleaning the system..........................41 Chassis installation..........................45 Installing units with JIC style (37° flare) valve connection and hoses..........45 Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 4
Appendix............................... 69 Limited warranty..........................73 Compressor - five year limited warranty..................74 Labor and cost not covered......................74 Exclusions..............................74 R-410A quick reference guide........................75 Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Note: Highlights additional information useful to the technician in completing the work being performed properly. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
November 2020 nomenclature Chassis Updated chassis nomenclature November 2020 nomenclature Associated literature Manual description Form number Vertical Stacked Heat Pump Start-Up and Performance Checklist 145.18-CL1 Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Riser nomenclature Note: VTR and VUR Single Risers are not available in reduce up or reduce down riser end options. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Chassis electrical and water connections are not installed. The chassis is secured to the service panel. Remove the screws before removing the service panel and chassis. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Secured it with nuts that are snug against the metal spacer sleeves. Inspect all electrical connections. Connections must be clean and tight at the terminals. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 12
All safety features, disengagement, and interlocks must be in place and function correctly before the equipment is put into operation. Never bypass or wire around any safety device. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
The risers are attached using nylon ties to allow for slight adjustments during installation, and expansion of riser column during operation. Care must be taken during installation to avoid damage to risers and riser stub-outs. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Note: Take extra care not to scrape or dent risers during positioning. The riser tailpiece should insert approximately 2 inches into the 3-inch long swaged section of the unit below. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 15
Center the riser stub-outs in the cabinet opening to allow for expansion and contraction. Riser stub-outs must not contact any sheet metal opening. Otherwise, damage can occur to the stub-outs, resulting in water leaks and property damage. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 16
DWDI forward-curved centrifugal / ECM direct-drive Diameter x width (in) 9x4T 9x4T 9x7T 9x7T 10x7T Motor HP 0.33 0.33 0.33 0.33 0.33 0.50 0.50 Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 17
* Nominal Capacity calculated in accordance with ARI/ISO Standard 13256-1 for Water Loop Application. ** Cabinet weight is approximate and does not include weight of risers. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Single riser cabinet dimensions Figure 3: Single riser cabinet and floor sleeve dimensions Table 2: Cabinet dimensions Model RA flange width (in.) 09–12 15–24 30–36 Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 19
A shut-off valve is not provided with the satellite side of the riser stub. Field-install shut- off valve with field hose kit (ordered separately). See Figure 8 for more details about installation. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Determine the riser shut-off valves and hose kits required for job-specific site conditions: Factory supplied risers come with the appropriate hose kits with Joint Industrial Committee (JIC) type fittings (see Figure 5). Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Hoses must be hand tightened then further tightened no more than 1/4 turn. DO NOT APPLY EXCESSIVE FORCE! WARNING Hoses must be hand tightened then further tightened no more than 1/4 turn. DO NOT APPLY EXCESSIVE FORCE! Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 22
Figure 5: Standard factory supplied JIC flare hose kits and risers Figure 6: Optional field supplied risers with factory supplied JIC flare hose kits and shut-off valves Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 23
Figure 7: Riser connections - standard style single riser Figure 8: Riser connections - master style single riser Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 24
The chassis water connections are marked using color labels indicating the correct water connections. The factory satellite stub-out connection is 5-1/2 inches. The field can extend it up to 24 inches. The shut-off valve is field-installed. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Locate thermostat away from supply drafts. Ensure the back of thermostat is sealed and protected from air drafts. Short cycling can result in damage to unit. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 26
Ensure that the control wiring between the thermostat and the unit’s terminations does not exceed 1 ohm. CAUTION Resistance in excess of 1 ohm may cause component damage due to insufficient AC voltage supply. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Mount the thermostat using the factory provided 1/4-inch number 8 screws. The ADA thermostat harness is plenum rated. It hangs in behind the RA door. For chassis servicing, unclip the harness from the unit switch plate. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Vacuum all the dust and construction debris from the unit drain pan, electrical box, and discharge plenum after cutting out the supply/return openings. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
A left hand opening door is shown. The RA panel with ADA is not reversible. It must be ordered in either a left or right hand opening configuration, determined by the location of the door hinge. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 30
16 1/4 20 3/4 +/- 1/8 15/18/24 25 3/4 19 1/4 23 3/4 +/- 1/8 30/36 29 3/4 23 1/4 27 3/4 +/- 1/8 Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 31
Note: For maximum RA flow, the flush mounted acoustic panel must be centered vertically and horizontally over the RA opening of the cabinet. Supply air duct collar extensions may be required to prevent short cycling. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 32
Figure 14: Return air (RA) panel dimensions Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Note: Ensure there is no direct contact between cabinet sheet metal parts and drywall enclosure. This includes RA and supply air flanges. Failure to follow these instructions will negatively affect unit sound performance. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
FPM ( Table and Table ) and divide by the supply grille free area factor. Figure 16: Supply grille with volume damper and 1/8-inch neoprene tape applied to its perimeter Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 35
Figure 17: Unit-mounted supply grille installation dimensions Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 36
Openings marked ‘N/A’ result in face velocities outside the recommended 300-500 FPM range. The Hi-Static Blower option or single horizontal discharge openings with unit-mounted supply grille are not recommended. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
23 for right and left hand version). The fresh air discharges upstream of the direct expansion (DX)coil through the discharge collector box. WARNING Do not allow incoming air to bypass the DX coil, otherwise damage to unit may occur. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Remove the seven fasteners holding the damper plate (see Figure 18). c. Drop down the plate and disconnect the quick-connect terminals from the harness. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 39
Figure 19: Remove the red cover If the black cover is loose, position it in place and slide it back onto the actuator (see Figure 20). Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Ensure that all air is bled from the system by cracking each air vent. Note: Make-up water must be available in sufficient volume to replace the volume occupied by the air that is bled off. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
The customer is responsible for completing adequate water loop maintenance over the lifespan of the units. Otherwise, damage to the units may occur. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 42
Figure 21: System flushing and cleaning Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 43
3. Optional front supply opening comes with 2-1/2 inch duct flange. 4. All other openings come with standard 1-inch duct flange. 5. Left and right hand versions shown. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 44
3. Optional front supply opening comes with 2-1/2 inch duct flange. 4. All other openings come with standard 1-inch duct flange. 5. Left and right hand versions shown. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Connect the hoses to the JIC fitting on the shut-off valves. Always use a backup wrench when tightening the hose to the valve fitting. Enable the hoses to hang free inside the cabinet. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 46
Insert the chassis midway into the opening of the cabinet. Lower the rear of the chassis until the base of the chassis touches the formed mounting rails in the cabinet drain pan. (See Figure 26.) Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 47
Pivot the chassis base on the front edge of the drain pan rails. Before fully inserting the chassis, ensure the wiring harness or water hoses cannot be pinched between the chassis and cabinet. (See Figure 27.) Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 48
The chassis should slide easily on the drain pan rails. Do not apply excessive force! Ensure that the chassis does not tip forward before removing the dolly. (See Figure 28.) Figure 27: Pivot the chassis Figure 28: Slide the chassis Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 49
When bleeding air from chassis system, ensure that return hose is inserted in cabinet drain pan properly. Do not fully open the supply riser. A steady stream of water is sufficient to force air through the chassis. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 50
18. Install the RA panel into the drywall opening if not already installed. See Acoustic RA panel. Secure the panel into the drywall with six screws. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
The compressor and blower amps are within the nameplate data values. The suction line is cool with no frost observed in the refrigerant circuit. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
High system loop temperatures may negatively affect unit performance, efficiency, maintenance and reliability, and noise levels. CAUTION Operating the unit below 40.0°F EWT can result in damage to the chassis circulation pump. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 53
90° elbows. Adding excessive pressure drop by means of field alterations to the piping system results in lower water flow of the pump. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Lock all electrical power supply switches in the OFF position before servicing the unit. Failure to disconnect power supply may result in electrical shock or even death. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Record the temperature of the liquid line at the oulet of the condenser. Subtract it from the saturation temperature for the corresponding discharge pressure. Figure 30: VSCS09 chassis with pump Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 56
990 970 950 930 910 890 865 845 820 795 770 740 710 680 650 615 575 High 795 785 775 760 745 730 715 695 675 655 630 605 580 Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 57
891 863 835 809 784 757 730 689 648 601 554 High High 1002 971 940 912 883 854 826 800 774 749 724 698 671 643 615 586 Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 58
891 863 835 809 784 757 730 689 648 601 554 971 940 912 883 854 826 800 774 749 724 698 671 643 615 586 Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Supply Min. CCT. CCT. BKR. size voltage ampacity 208-230/1/60 22.0 0.10 5.79 208-230/1/60 25.0 0.17 7.54 208-230/1/60 29.0 0.17 8.66 208-230/1/60 48.0 0.25 13.21 Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 60
Supply Min. CCT. CCT. BKR. size voltage ampacity 208-230/1/60 22.0 0.33 5.98 208-230/1/60 25.0 0.33 7.34 208-230/1/60 29.0 0.33 9.46 208-230/1/60 48.0 0.33 13.71 Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 61
Supply Min. CCT. CCT. BKR. size voltage ampacity 265/1/60 23.0 0.33 5.47 265/1/60 26.3 0.33 7.30 265/1/60 28.0 0.33 8.55 265/1/60 43.0 0.33 11.19 Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 62
Max fuse/ Unit Supply Min. CCT. CCT. BKR. size voltage ampacity 265/1/60 54.0 0.33 14.31 265/1/60 11.2 60.0 0.50 17.04 265/1/60 13.5 72.0 0.50 19.92 Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Otherwise, the unit operates the cooling system until the minimum runtime for the compressor completes. After the compressor de-energizes and the time for fan off delay elapses, the blower stops. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
If a low pressure limit switch opens three times within 1 hour of operation, the microprocessor control board locks out the compressor (a hard lockout) and flashes a fault code (see Table 23). Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Additionally, a minimum runtime is imposed any time a compressor energizes. The ASCD initates on unit start-up and on any compressor reset or lockout. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Note: * These flash codes do not represent alarms. Communication ™ The communication protocol is Modbus using the RTU method of packet framing at 19200-baud rate. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Bacteria/mold Iron Oxide Less than 1 ppm Less than 1 ppm Calcium & Magnesium Scaling Less than 350 ppm Less than 350 ppm Carbonate Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 68
Calcium Chloride/Sodium Less than 125 ppm Less than 125 ppm Chloride Chlorine Less than 0.5 ppm Less than 0.5 ppm Hydrogen Sulfide None None Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Appendix Figure 32: PSC motor wiring diagram Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 70
Figure 33: ECM wiring diagram Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 71
Figure 34: Continuous fan with ECM wiring diagram Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Page 72
Figure 35: Motorized damper ECM wiring diagram Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...
Limited Warranty. When a defective part can be repaired or replaced, Johnson Controls shall not be obligated to repair the entire unit or any part thereof other than the defective part.
Compressor - five year limited warranty In addition to the 1 year Limited Warranty, Johnson Controls warrants the compressor to be free from defects in workmanship or material for a period of 5 years from the date of original installation. If a compressor fails during this five year period, a new compressor will be supplied.
Never open system to atmosphere when under vacuum. • If system must be opened for service, evacuate system then break the vacuum with dry nitrogen and replace filter driers. Single Riser Hi-Rise Water Source Heat Pump, Cabinet Model VBR/VMR/VTR/VUR09-36 and Chassis Model VSCS09-36 Johnson Controls...