Reactive Power Control With Setpoint Command Via Modbus Protocol: Varctlcom Mode; Reactive Power Control With Setpoint Command Via Modbus Protocol: Pfctlcom Mode; Reactive Power Control With Absolute Value: Varcnst Mode; Reactive Power Control As A Percentage Of The Nominal Power: Varcnstnom Mode - SMA SUNNY CENTRAL 500CP-JP User Manual

Hide thumbs Also See for SUNNY CENTRAL 500CP-JP:
Table of Contents

Advertisement

SMA Solar Technology AG
8.2.1.3
Reactive Power Control with Setpoint Command via Modbus Protocol:
VArCtlCom Mode
The reactive power setpoint is received by the Sunny Central via the Power Reducer Box or the Power Plant Controller.
The setpoint is transmitted as a percentage and converted to kVAr in the device.
If the Sunny Central has not received any signal for the last five minutes, the error message Q-VArModFailStt will be
displayed (see Section 8.2.2, page 63).
8.2.1.4
Reactive Power Control with Setpoint Command via Modbus Protocol: PFCtlCom
Mode
The reactive power setpoint is received by the Sunny Central via the Power Reducer Box or the Power Plant Controller.
The setpoint is transmitted as a displacement power factor cos φ.
If the Sunny Central has not received any signal for the last five minutes, an error message will be displayed in the
instantaneous value Q-VArModFailStt (see Section 8.2.2, page 63).
8.2.1.5

Reactive Power Control with Absolute Value: VArCnst Mode

The Q-VAr parameter is used to set the reactive power setpoint. The permitted range of the parameter Q-VAr is between
‒Qmax and +Qmax.
8.2.1.6
Reactive Power Control as a Percentage of the Nominal Power: VArCnstNom
Mode
The parameter Q-VArNom is used to set the reactive power setpoint in %. The parameter Q-VArNom refers to Pmax.
If the calculated amount of reactive power exceeds the predefined value of Qmax, the power will be limited to Qmax.
If the calculated amount of reactive power falls below the predefined value of ‒Qmax, the power will be limited to
‒Qmax.
8.2.1.7

Reactive Power Setpoint via Standard Signal: VArCnstNomAnIn Mode

The reactive power setpoint is set via an analog signal at the input terminals for setpoint specification (see Sunny Central
installation manual). This is usually implemented by a ripple control signal.
The analog value is converted into a reactive power setpoint. The electrical current strength of the connected signal
determines the setpoint.
The analog measured values must be between 4 mA and 19 mA. If the analog signal is less than 2 mA, an error message
will be displayed in the instantaneous value Q-VArModFailStt (see Section 8.2.2, page 63).
Signal
< 2 mA
Last valid mean value or
0 kVAr after restart
2 mA to 4 mA
4 mA
11.5 mA
> 19 mA
The analog value is converted to a setpoint for power limitation. Here, the Qmax parameter forms the end point of the
linear characteristic curve.
User Manual
Power limit
Description
Signal is in the invalid range.
− Pmax
The maximum amount of negatively excited reactive power is fed in.
− Pmax
Start point of the characteristic curve
The maximum amount of negatively excited reactive power is fed in.
0 kVAr
Zero-crossing of the characteristic curve
No reactive power is fed in.
+Pmax
End point of the characteristic curve
The maximum amount of positively excited reactive power is fed in.
SCCP-JP-BA-A4-en-12
8  Power Control
55

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sunny central 630cp-jpSunny central 800cp-jp

Table of Contents