Measures For Voltage Support Through Parameterization Of Reactive Power/Voltage Characteristic Curve: Varctlvolhystdba Mode - SMA SUNNY CENTRAL 500CP-JP User Manual

Hide thumbs Also See for SUNNY CENTRAL 500CP-JP:
Table of Contents

Advertisement

8  Power Control
8.2.1.13 Measures for Voltage Support through Parameterization of Reactive Power/
Voltage Characteristic Curve: VArCtlVolHystDbA Mode
Contact the SMA Service Line before changing any parameters.
The SMA Service Line must be consulted prior to selection and parameterization of the VArCtlVolHysDbA mode.
By provision of reactive power, the inverter helps perform voltage-stabilizing measures in the event of overvoltage or
undervoltage. The parameterization is carried out by means of a reactive power/voltage characteristic curve.
The characteristic curve can be configured flexibly by parameterization of the slopes, a type of deadband through two
voltage points, a hysteresis and the thresholds for activation.
Figure 26: Characteristic curve for reducing reactive power with deadband and hysteresis
The parameter Q-VArTmsSpnt determines the delay time which must elapse before the calculated reactive power
setpoint is actively used.
In order to prevent mutual interference of several systems with this function, the parameter Q-VArTmsVtg can be used
to set a delay time. This delay time defines how long a voltage change must be pending before a change in reactive
power feed-in is triggered. Consequently, control of the line voltage at the grid feed-in point can be staggered across
several systems.
You can activate and deactivate the delay time by means of the parameter Q-EnaTmsVtg.
In addition, the parameter Q-VLockInTm can be used to define a voltage at which reactive power control will be
activated after the time specified in parameter Q-VLockInTm has elapsed. If the voltage exceeds the threshold defined
in parameter Q-VLockOutW, the reactive power control will be deactivated once the time specified in parameter
Q-VLockOutTm has run out.
62
SCCP-JP-BA-A4-en-12
SMA Solar Technology AG
User Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sunny central 630cp-jpSunny central 800cp-jp

Table of Contents