List of Error Messages
PC Interface Errors
Error
Error message
code
0080
No message.
0081
No message.
0082
No message.
0083
No message.
0084
---
0085
No message.
0086
No message.
0087
---
0088
---
0089
---
DM Setting Errors
Error
Error message
code
0090
No message.
0091
No message.
0092
No message.
0093
No message.
0094
No message.
0095
No message.
0096
No message.
0097
No message.
0098
No message.
0099
No message.
Probable cause
The IOWR/IORD instruction is
incorrect.
Incorrect number of transfer (read/
write) words in the IOWR/IORD
instruction.
Interrupt to the ASCII Unit using the
IOWR (#CC00) instruction is incorrect.
When reading and writing to the shared
memory using the IOWR/IORD
(#00
) instruction, the first read/write
@ @
word (offset word
from the
@ @
beginning of the IOWR/IORD Area) is
incorrect.
Not used.
ON PC interrupt number is out of range. Use 01 to 99.
The PC interrupt number is an illegal
BCD value.
Not used.
Not used.
Not used.
Probable cause
Incorrect setting for program number at
startup (DM Area allocations).
Incorrect automatic transfer settings
from flash ROM (DM Area allocations).
Incorrect Start Mode settings (DM Area
allocations).
Incorrect initial value transfer settings
(DM Area allocations)
Not used (DM Area allocations).
Incorrect baud rate parameters for port
1, 2, or terminal (DM Area allocations).
Incorrect number of transfer words per
cycle (DM Area allocations).
Invalid screen size or terminal mode.
The first transfer word setting for the
IORD or IOWR Area is incorrect (DM
Area allocations).
Invalid DMA option (port 1 or 2)
Corrective measures
Check the operands for the IOWR/
IORD instructions.
Set the IOWR/IORD (#00
instruction to a maximum of 90 words
and the IOWR/IORD (#FD00)
instruction to a maximum of 128 words.
Check whether or not the
IOWR(#CC00) instruction interrupt
number matches the ON PC (interrupt
number) command.
Check the offset word
@ @
IORD (#00
) instruction and the first
@ @
words of the IOWR Area and IORD
Area (m + 6 and m + 7 in the DM Area
allocations).
---
Use a valid BCD value.
---
---
---
Corrective measures
Set any between 00 and 04 (BCD).
Set either 00 or 5A
.
hex
Set either 00 or 5A
.
hex
Set either 0 or 1 (BCD).
Set 0 (BCD).
Set any of 00 to 08 (BCD).
After checking that the PC is a
C200HX/HG/HE or CS1-series PC, set
either 00 or 5A
.
hex
Set the specified value within the
proper range.
Set either 00, or between 10 and 99
(BCD).
Set either 00 or 5A
.
hex
Section 9-1
)
@ @
in the IOWR/