Input Registers; Holding Registers; Scaling Sample - HindlePower AT10.1 Series Operating Instructions Manual

Microprocessor-controlled float battery charger communications module
Hide thumbs Also See for AT10.1 Series:
Table of Contents

Advertisement

MODBUS

8.3.3 Input Registers

Address
Name
30001
Communication Firmware Rev.
30002
DNP Rev
30003
AT10.1 Firmware Rev
30004
Voltage Rating
30005
Current Rating
30006
Voltage
30007
Current
30008
Equalize Time Remaining
30009
Error Number
30010
Battery Temperature

8.3.4 Holding Registers

Address
Name
40001
Float Voltage Setpoint
40002
Equalize Voltage Setpoint
40003
Equalize Time
40004
Current Limit
40005
HVDC Setpoint
40006
LVDC Setpoint

8.3.5 Scaling Sample

Reading address 30006 Voltage returns a value of 1300. The multiplier for that address is 10
(1300 / 10 = 130.0). Setting the Float Voltage Setpoint 40001 to 125.0 Vdc requires setting
the address 40001 to 1250 because the multiplier is 10. 125.0 x 10 = 1250.
32
Description
Software Revision
Software Revision
Software Revision
Charger Voltage Rating
Charger Current Rating
Output Voltage
Output Current
Equalize Time Remaining in Hours
Self Diagnostic Error Codes
Temperature in Celsius
Description
Float Voltage Setpoint
Equalize Voltage Setpoint
Equalize Time in Hours
Current Limit in Amperes
High Voltage DC Alarm Setpoint
Low Voltage DC Alarm Setpoint
Multiplier
100
100
100
1
1
10
10
1
1
1
Multiplier
10
10
1
10
10
10

Advertisement

Table of Contents
loading

This manual is also suitable for:

At30 seriesAt10.1 g1At10.1 g2

Table of Contents