8.3

Register Definitions

8.3.1 Binary Outputs

Address
Name
00001
Equalize Mode
00002
Manual Timer Method
00003
Manual Equalize Method
00004
Auto-Equalize Timer Method
00005
HVDC Shutdown Enable
00006
Battery Type
- -NOTICE- -
Only one (1) equalize method can be active at a time. The equalize method
cannot be turned off. By turning on one (1) of the equalize methods the charger will turn off
the other two (2) equalize methods automatically.

8.3.2 Binary Inputs

Address
Name
10001
HVDC
10002
LVDC
10003
DC Output Failure
10004
AC Input Failure
10005
Positive Ground Fault
10006
Negative Ground Fault
10007
CAR
10008
HVDC Shutdown
10009
LVAC Shutdown
10010
FLS Enabled
10011
Temperature Probe Installed
10012
Defective Temperature Probe
Description
1=Equalize Mode, 0=Float Mode
Equalize Method (see notice below)
Equalize Method (see notice below)
Equalize Method (see notice below)
Enables High Voltage DC Shutdown
0=Lead, 1=NiCd, Used for TempCo
Description
High Voltage DC Alarm
Low Voltage DC Alarm
Charger Failure Alarm
AC Input Failure Alarm
Positive Ground Fault Alarm
Negative Ground Fault Alarm
Summary (Common) Alarm Relay
High Voltage DC Shutdown Enabled
Low Voltage AC Shutdown Enabled
Forced Load Share Enabled
Temperature Probe Installed
Defective Temperature Probe Alarm