If S1-2 is set to OFF for using factory default values, the parameters can be viewed. The
parameters can be modified, but if S1-2 is still OFF (set to factory default values) when the
Communications board is reset, all values will be changed back to factory defaults. Setting
S1-2 to ON will allow user values to be used. If S1-2 is OFF, the screen will look like this:
-- EN5004 Setup --
USING DEFAULT VALUES. (SWITCH S1-2 IS OFF)
CHANGED VALUES WILL NOT BE STORED
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
To change a value or RESTART, please select its item number:
After all parameters have been modified to the correct values, turn off switch S1-1. Select
"RESTART Comm Board" on terminal main menu. Close your terminal program and
reconnect the charger to the communications network. Make sure all switch settings are set
correctly.

4.3 Factory Defaults

Configuration Parameter
DNP Device Address:
DNP Unsolicited Destination Address:
DNP Unsolicited Messaging Enabled:
DNP Unsolicited Timeout:
DNP Unsolicited Retries Amount:
DNP Unsolicited Indefinite Retries:
Comm Parity:
Comm Stop Bits:
IP Address:
Netmask:
Gateway:
Enable Modbus over TCP/IP:
Modbus TCP Port:
Enable DNP over TCP/IP:
DNP TCP Port:
16
DNP Device Address (1)
DNP Unsol Destination Address (65519)
DNP Unsol Messaging Enable (0=disabled)
DNP Unsol Timeout (30)
DNP Unsol Retries Amount (2)
DNP Unsol Indefinite Retries (0)
Comm Parity (0=none)
Comm Stop Bits (1)
IP Address (192.168.1.100)
Netmask (255.255.255.0)
Gateway (0.0.0.0)
Enable Modbus over TCP/IP (0=disabled)
Modbus TCP Port (502)
Enable DNP over TCP/IP (0=disabled)
DNP TCP Port (20000)
RESTART Comm Board
Factory Default
1
65519
0 (Off)
30 seconds
2
0 (Off)
0 (None)
1
192.168.1.100
255.255.255.0
0.0.0.0
0 (disable)
502
0 (disabled)
20000
Range
1 to 65519
1 to 65519
0 (Off), 1 (On)
1 to 60 seconds
0 to 255
0 (Limited), 1 (Indefinite)
0 (None), 1 (Odd), 2 (Even)
1 or 2
255.255.255.255
255.255.255.255
255.255.255.255
0(disable),1(enable)
0 to 65535
0(disable),1(enable)
0 to 65535