Setup Program - HindlePower AT10.1 Series Operating Instructions Manual

Microprocessor-controlled float battery charger communications module
Hide thumbs Also See for AT10.1 Series:
Table of Contents

Advertisement

4.2

Setup Program

The setup program may only be used with an RS-232 serial connection. See Figure 3. Use
a terminal mode program such as HyperTerminal with the baud rate set to 9600 bps, 8 data
bits, no parity, 2 stop bits, and no hardware handshaking. To enable the setup program, set
switch S1-1 to ON. To use the user values for configuration parameters, set switch S1-2 to
ON. The following screen will appear:
-- EN5004 Setup --
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
To change a value, please select its item number:
To select an item to view and modify, enter the item number by typing the number and press
ENTER. The sample below shows item 1 DNP Device Address is selected. The current
value is set to 1. Entering a new value and pressing ENTER will accept the new value if it is
within the acceptable range. "Value written to memory" will be displayed if
accepted or "VALUE ENTERED IS OUT OF RANGE!" if not accepted. Pressing the ESC
key will cancel modifying the parameter and return to main menu.
To change a value or RESTART, please select its item number: 1
DNP Device Address: 1 (Range 1 to 65,519),
Enter new value (ESC to cancel): 1
Value written to memory
DNP Device Address (1)
DNP Unsol Destination Address (65519)
DNP Unsol Messaging Enable (0=disabled)
DNP Unsol Timeout (30)
DNP Unsol Retries Amount (2)
DNP Unsol Indefinite Retries (0)
Comm Parity (0=none)
Comm Stop Bits (1)
IP Address (192.168.1.100)
Netmask (255.255.255.0)
Gateway (0.0.0.0)
Enable Modbus over TCP/IP (0=disabled)
Modbus TCP Port (502)
Enable DNP over TCP/IP (0=disabled)
DNP TCP Port (20000)
RESTART Comm Board
CONFIGURATION
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

At30 seriesAt10.1 g1At10.1 g2