HindlePower AT10.1 Series Operating Instructions Manual page 26

Microprocessor-controlled float battery charger communications module
Hide thumbs Also See for AT10.1 Series:
Table of Contents

Advertisement

DNP V3.00
OBJECT
Object
Variation
Number
Number
50
0
Time and Date
50
1
Time and Date
(default -
see note 1)
60
0
Class 0, 1, 2, and 3 Data
60
1
Class 0 Data
60
2
Class 1 Data
60
3
Class 2 Data
60
4
Class 3 Data
No Object (function code only) see note 3
No Object (function code only)
No Object (function code only)
Note 1: A Default variation refers to the variation responded when variation 0 is requested
and/or in class 0, 1, 2, or 3 scans. Default variations are configurable. However, default
settings for the configuration parameters are indicated in the table above.
Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a
request is sent with qualifiers 17 or 28, respectively. Otherwise, static object requests sent
with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01. For change-
event objects, qualifiers 17 or 28 are always responded except for object 70, which responds
with qualifier 1B or 5B.
Note 3: For the AT Communications Module, a cold restart is implemented as a warm
restart. The executable is not restarted, but the DNP process is restarted.
Note 4: Writes of Internal Indications are only supported for index 7 (Restart IIN1-7), and
indices 16 and beyond (user-defined indications).
24
Function
Description
Codes (dec)
1
1
2
1
20
21
1
22
1
20
21
22
1
20
21
22
1
20
21
22
13
14
23
REQUEST
(Library will parse)
Qualifier Codes
(hex)
00, 01
(read)
(start-stop)
06
(no range, or all)
07, 08
(limited qty)
17, 28
(index)
00, 01
(read)
(start-stop)
06
(no range, or all)
07
(limited qty=1)
08
(limited qty)
17, 28
(index)
00, 01
(write)
(start-stop)
07
(limited qty=1)
08
(limited qty)
17, 28
(index)
06
(read)
(no range, or all)
(enbl. unsol.)
(dsbl. unsol.)
06
(read)
(no range, or all)
(assign class)
06
(read)
(no range, or all)
07, 08
(limited qty)
06
(enbl. unsol.)
(no range, or all)
(dsbl. unsol.)
(assign class)
06
(read)
(no range, or all)
07, 08
(limited qty)
06
(enbl. unsol.)
(no range, or all)
(dsbl. unsol.)
(assign class)
06
(read)
(no range, or all)
07, 08
(limited qty)
06
(enbl. unsol.)
(no range, or all)
(dsbl. unsol.)
(assign class)
(cold restart)
(warm restart)
(delay meas.)
RESPONSE
(Library will respond with)
Function
Qualifier Codes
Codes (dec)
(hex)
129
00, 01
(response)
(start-stop)
17, 28
(index –
see note 2)
129
00, 01
(response)
(start-stop)
17, 28
(index –
see note 2)