7

DNP V3.00

7.1 Introduction

This manual section describes the specific implementation of the DNP3 Level 2 protocol via
the AT Series Battery Charger Communications Module interface (p/n EJ5037-##). This
section, in conjunction with the DNP3 Basic 4 Document Set, and the DNP Subset
Definitions Document, provides complete information on how to communicate.
This implementation of DNP3 is fully compliant with DNP3 Subset Definition Level 2,
contains many Subset Level 3 features, and contains some functionality even beyond Subset
Level 3.
7.2

Device Profile

The following table provides a "Device Profile Document" in the standard format defined in
the DNP3 Subset Definitions Document. While it is referred to in the DNP3 Subset
Definitions as a "Document," it is only a component of a total interoperability guide. This
table, in combination with the following should provide a complete interoperability /
configuration guide for the AT Series Communications Module interface:
• The Implementation Table provided in Section 7.3 on page 22
• The Point List Tables provided in Section 7.4 on page 25
DNP V3.00
DEVICE PROFILE DOCUMENT
(Also see the Implementation Table in Section 7.3 on page 22.)
Vendor Name: HindlePower, Inc. - 1075 Saint John Street - Easton, PA 18042
Device Name: Communications Module interface (manufacturer's p/n EJ5037-##)
Highest DNP Level Supported:
For Requests:
For Responses:
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported
(the complete list is described in the attached table):
Maximum Data Link Frame Size (octets):
Transmitted:
Received
Maximum Data Link Re-tries:
None
Fixed at 3
Configurable range 0 to 255
Requires Data Link Layer Confirmation:
Never
Always
Sometimes
Configurable
Device Function:
Level 2
Level 2
Maximum Application Fragment Size (octets):
292
292
Maximum Application Layer Re-tries:
Master
Slave
Transmitted:
2048
Received:
2048
None
Configurable