7.4
Point List
The tables in the following sections identify all the individual data points provided by this
implementation of DNP3.
7.4.1 Binary Inputs
Binary Input Points
Static (Steady-State) Object Number:
Change Event Object Number:
Request Function Codes supported:
Static Variation reported
when variation 0 requested:
Change Event Variation reported
when variation 0 requested:
Change Event Scan Rate:
Point
Name/Description
Index
0
HVDC Alarm (1 = active)
1
LVDC Alarm (1 = active)
2
DC Output Failure Alarm (1= active)
3
AC input Failure Alarm (1 = active)
4
Positive Ground Fault Alarm (1 = active)
5
Negative Ground Fault Alarm (1 = active)
6
CAR (Summary) Alarm (1 = active)
7
HVDC Shutdown (1 = active)
8
LVAC Shutdown (1 = active)
9
Forced load sharing enabled (1 = enabled)
10
Temperate probe installed (1 = installed)
11
Defective temperate probe (1 = defective)
12
Equalize Mode - status of Binary Output: 0 (0 = float; 1 = equalize)
13
Manual Timer Method - status of Binary Output 1 (1 = enabled)
14
Manual Equalize Method - status of Binary Output 2 (1 = enabled)
15
Auto-Equalize Timer Method - status of Binary Output 3 (1 = enabled)
16
HVDC Shutdown Enabled - status of Binary Output 4 (1 = enabled)
17
Battery Type - status of Binary Output 5 (0= Lead; 1 = NiCD)
1
2
1 (read)
22 (assign class)
1 (Binary Input Without Status)
2 (Binary Input Change with Time)
As indicated below, the scan rate for binary input
change events is 5000 ms)
DNP V3.00
Initial Change Event Class
(1, 2, 3 or none)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
25