How To Install The Remote Sensor - Sanyo ECO-i AHX0752 Technical Data Manual

Hide thumbs Also See for ECO-i AHX0752:
Table of Contents

Advertisement

6. Remote Sensor

How to Install the Remote Sensor

NOTE
Do not twist the remote sensor wiring with the power wiring or run it in the same metal conduit, because
this may cause malfunction.
Install the remote sensor away from sources of electrical noise.
Install a noise fi lter or take other appropriate action if electrical noise affects the power supply circuit of
the unit.
Use an electric junction box (supplied locally) (Fig. 3-47) for fl ush mounting of the remote sensor.
1
2
3
4
5
1.
Insert a screwdriver or the like in the groove on the lower side of the remote sensor body to pry off the
back case. (Fig. 3-48)
2.
Use the 2 supplied M4 or 5/32" machine screws to secure the remote sensor back case. Prior to
mounting, clear the cutouts in the back case corresponding to the holes in the wall box using a screw-
driver or the like. Use the spacers and take care not to tighten the screws excessively. If the back case
will not seat well, cut the spacers to a suitable thickness.
6
3.
Connect locally supplied 2 core lead wires to the lead wires from the remote sensor. (See "How to wire
the remote sensor.")
When connecting the locally supplied 2 core lead wires to the terminal block, check the termi-
nal numbers in the indoor unit to make sure that the wires are correctly connected. (Fig. 3-49)
(The remote sensor is damaged if 208 / 230V AC is applied.)
4.
Fit the remote sensor to the tabs of the back case and mount it.
7
8
Under case (back case)
Simplified remote controller
Machine screws
M4 × 25 or 5/32" × 1"
Control of W-3WAY ECO-i SYSTEM
Spacer
Electric junction box
for one box (no cover)
3-68
Wall
Fig. 3-47
Fig. 3-48

Hide quick links: