2. Indoor Unit Control PCB Switches and Functions

Indoor Unit Control PCB Switches and Functions

Indoor unit control PCB
T10:
6P plug (yellow): Used for remote control. (Refer to the remote control section.)
(CN61)
Control items: (1) Start/stop input
EXCT:
2P plug (red): Can be used for demand control. When input is present, forces the unit to operate with the thermostat
OFF.
(CN73)
DISP:
2P plug (white): Short-circuiting this plug allows the unit to be operated by the remote controller, even if it is not
(CN72)
connected to an outdoor unit.
(In this case, alarm "E04," which indicates trouble in the serial communication between the indoor and outdoor unit,
does not occur.)
CHK:
2P plug (white): Test pin. Short-circuiting this pin allows the indoor FM (H fan speed), drain pump, fl ap motor (F1
position), and electronic expansion valve full-open position to be checked.
However this function turns OFF if the indoor unit protection mechanism is activated. The unit can be operated even
if the remote controller and outdoor unit are not connected. However even if the remote controller cannot is con-
nected, it cannot be used to operate the unit. This function can be used for short-term tests.
JP1:
Jumper wire: Allows selection of the T10 terminal start/stop signal. (Refer to the remote control section.) Status at
(J01)
shipment: Pulse signal
Jumper wire cut: Static signal (continuous signal)
FAN DRIVE 2P plug (white): This terminal sends a signal to the ventilation fan when the FAN button on the wired remote con-
troller is used to operate a commercially-available ventilation fan. (Refer to the remote control section.)
Use a ventilation fan which can accept no-voltage A contact as the external input signal.
FILTER:
2P (white): This terminal is used to connect contact input from the differential pressure switch which detects fi lter
(CN70)
clogging. When the contacts turn ON, "FILTER" is displayed on the wired remote controller.
Power LED: LED (red): Illuminates when power is supplied. Blinks when there is a failure in the EEPROM (IC10: nonvolatile
memory).
EEPROM:
Nonvolatile memory: Memory which stores the unit type data and other information. When the PCB is replaced,
(IC10)
remove the EEPROM from the old PCB and install it onto the new PCB. If an IC failure occurs, replace with a new IC
which was provided with the service PCB, and set the necessary information from the wired remote controller. (For
the procedure, refer to the servicing technical materials.)
GRL:
For AC fan motor (CR-UXRP71B-B: 3P (yellow))
(CN20)
For DC fan motor (CR-SXRP56B-B: 5P (blue))
The indoor unit power terminal plate may be a 7P type or may be a 5P type. (Refer to the fi gure at below.) The basic wiring
diagram shows the 7P-type terminal plate. Therefore the terminal plate may differ from the illustrations.
(2) Remote controller prohibit input
(3) Start signal output
(4) Alarm signal output
7P-type terminal plate
7P-type terminal plate
1(L1) 2(L2)
U1 U2
R1 R2
Power
Inter-unit
Remote
supply
control wiring
controller
7-7
PCB and Functions
5P-type terminal plate type
5P-type terminal plate
1
2
3
4
5
1(L1) 2(L2)
U1
U2
Power
Inter-unit
supply
control wiring
1
2
3
4
5
6
7
8