4. System Controller

■ Mode setting

According to function of each system controller, set
SW1 as Fig. 3-33.
(1)
Central control/Remote control mode
● Central control mode
System controller is used as central control equip-
ment.
Individual setting by remote controller can be
inhibitted by system controller
● Remote control mode
System controller is used as remote controller.
Setting by system controller is inhibitted by other
central control equipments.
(2)
ALL/ZONE mode
1
● ALL mode
All indoor units can be controlled by system control-
ler.
● ZONE mode
Indoor units in one of ZONE 1, 2, 3 or 4 can be
2
controlled by system controller
(3)
Function of system controller is 10 types accord-
ing to combination of central control/remote
control mode and ALL/ZONE mode setting as the
table 9-1.
3
(4)
Stick the system controller unit label in a con-
spicuous position.
4
5
6
7
8
Control of W-3WAY ECO-i SYSTEM
Central control
Remote control
mode
mode
2
3 4 5 6
2
3 4 5 6
ON
ON
OFF
OFF
ALL
ALL
central control
remote control
2
3 4 5 6
2
3 4 5 6
ON
ON
OFF
OFF
ZONE1
ZONE1
central control
remote control
2
3 4 5 6
2
3 4 5 6
ON
ON
OFF
OFF
ZONE2
ZONE2
central control
remote control
2
3 4 5 6
2
3 4 5 6
ON
ON
OFF
OFF
ZONE3
ZONE3
central control
remote control
2
3 4 5 6
2
3 4 5 6
ON
ON
OFF
OFF
ZONE4
ZONE4
central control
remote control
Fig. 3-33
Table 9-1
Central control
ALL
1. ALL/Central
ZONE1
2. ZONE1/Central
ZONE2
3. ZONE2/Central
ZONE3
4. ZONE3/Central
ZONE4
5. ZONE4/Central
3-52
Inter-unit control wiring
1
2
16
ZONE1
central control
address 1-16
17
18
32
ZONE2
central control
address 17-32
33
34
48
ZONE3
central control
address 33-48
49
50
64
ZONE4
central control
address 49-64
2048_M_I
Remote control
6. ALL/Remote
7. ZONE1/Remote
8. ZONE2/Remote
9. ZONE3/Remote
10. ZONE4/Remote