4. Installation Instructions
Installation of Solenoid Valve Kit
1. Install the relay kit into the indoor unit.
Refer to the Installation Manual for the solenoid valve kit.
2. Connect the solenoid valve kit and the relay kit in the field.
Relay kit
1
NOTE
Notes on Installation
2
Be sure to secure the valve body by using its structure with the suspension bolt, etc.
Install the valve body within a distance of 98 ft. from the indoor unit.
Some refrigerant noise will be produced. Therefore in hospitals, libraries, hotel guest rooms, and other quiet locations, it is
recommended that the solenoid valve kit be installed on the ceiling reverse side of a hallway or another location separated
from the room.
When installing the valve body, install with the top surface facing up. Secure 7-7/8" or more of space to the front so that the
3
front service panel can be removed.
If the supplied suspension hook will not be used, and other fastening devices will be attached in the fi eld, use the 4 screw
holes on the top surface. DO NOT use any long screws other than the supplied screws. Use of other screws may puncture
the internal tubing, resulting in refrigerant leakage.
Do not block the air holes.
4
Suspension bolt (3/8" or M10) (field supplied)
5
Washer
Suspension hook
6
7
8
Liquid tube
Connect with
conduit for
power supply
Front
Nut (field supplied) (3/8" or M10)
M4 screws
(12 pcs.)
Design of W-3WAY ECO-i SYSTEM Unit Specifi cations
Gas tube
Suction tube
Cover of control box
2-44
Suspension hook
Top surface
Discharge tube
Liquid tube
Front
Service space