Outing Function - Sanyo ECO-i AHX0752 Technical Data Manual

Hide thumbs Also See for ECO-i AHX0752:
Table of Contents

Advertisement

3. Timer Remote Controller

Outing Function

Outing function is a function that prevents the room temperature from increasing too much (or decreasing too much) when no
one is in the room.
An air conditioner works automatically if this function is set effective.
General Performance of the Outing Function
COOL / DRY
The air conditioner starts operation when the room tem-
perature increases up to –1°F of the upper limit.
The air conditioner stops operation when the room tem-
perature decreases up to –2°F of the upper limit.
HEAT
The air conditioner starts operation when the room tem-
perature decreases up to +1°F of the lower limit.
The air conditioner stops operation when the room tem-
perature increases up to +2°F of the lower limit.
[Precautions]
The outing control only starts/stops the air conditioner. It does not change the operation mode/temperature setting.
Therefore, the operation mode/temperature needs to be set beforehand so that the outing function turns on the air condition-
er with your desired operation mode/ temperature setting.
If the room temperature rapidly changes, the room temperature may get over the upper or lower limit when the outing func-
tion is activated.
The outing function is invalid during FAN/AUTO operation mode.
The air conditioner's stop order (stated in
If operated using other remote control unit (or a centralized control device such as a system control), the outing function does
not work.
/above) is valid only when the outing function is operated.
3-37
Control of W-3WAY ECO-i SYSTEM