3. Electrical Wiring

3-1. General Precautions on Wiring
(1) Before wiring, confi rm the rated voltage of the unit
as shown on its nameplate, then carry out the wiring
closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for
each unit, and a power supply disconnect and circuit
breaker for overcurrent protection should be provided
in the exclusive line.
(3) To prevent possible hazards from insulation failure,
the unit must be grounded.
(4) Each wiring connection must be done in accordance
with the wiring system diagram. Wrong wiring may
cause the unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be
very dangerous. The manufacturer will accept no re-
3-2. Recommended Wire Length and Wire Diameter for Power Supply System Outdoor unit
Outdoor unit
1
CHDZ09053
CHDZR09053
CHDZ14053
2
CHDZR14053
Indoor unit
Type
3
K
A, X, XM, T, U
D (364, 484)
Control wiring
4
(A) Inter-unit (between outdoor and
indoor units) control wiring
AWG #18 (0.75 mm
Use shielded wiring*
Max. 3,280 ft.
5
NOTE
* With ring-type wire terminal.
6
7
8
Time delay fuse or
circuit capacity
50 A
70 A
Time delay fuse or
circuit capacity
10 – 16 A
10 – 16 A
10 – 16 A
(B) Remote control wiring
2
)
AWG #18 (0.75 mm
Use shielded wiring
Max. 1,640 ft.
Design of W-3WAY ECO-i SYSTEM Unit Specifi cations
sponsibility for any damage or misoperation that occurs
as a result of such unauthorized changes.
(7) Regulations on wire diameters differ from locality to
locality. For fi eld wiring rules, please refer to your LOCAL
ELECTRICAL CODES before beginning.
You must ensure that installation complies with all rel-
evant rules and regulations.
(8) To prevent malfunction of the air conditioner caused by
electrical noise, care must be taken when wiring as fol-
lows:
The remote control wiring and the inter-unit control wiring
should be wired apart from the inter-unit power wiring.
Use shielded wires for inter-unit control wiring between
units and ground the shield on both sides.
(9) If the power supply cord of this appliance is damaged,
it must be replaced by a repair shop appointed by the
manufacture, because special purpose tools are re-
quired.
(C) Control wiring for group control
2
)
(D) Inter-outdoor unit control wiring
2-24
2
AWG #18 (0.75 mm
)
Use shielded wiring
Max. 1,640 ft. (Total)
2
AWG #18 (0.75 mm
)
Use shielded wiring
Max. 1,640 ft.