GOOSE receiving block (GOSUBBLK)
(ii)
This is used for receiving or rejecting GOOSE subscription information from another IED for
testing bad reception. See Chapter
Test flag cancel (S-TestFlagCancel)
(iii)
Test flag in the communication packet will be removed unconditionally, when On is set for
setting [Test flag].
Test for all communication (TestFlag-EN)
(iv)
Setting [TestFlag-EN]=On allows to set test flags at all communication protocol (see Chapter
User interface: Test-submenu
Test for relay application
13.4.2
Auto monitoring function (A.M.F)
(i)
Issuing alarms will be blocked when Off is set for [A.M.F]. For the content about the monitoring
function, see Chapter
Test for CB and DS at CH (Replica_CHxx)
(ii)
If CB or DS should to be closed or open temporarily for testing, use settings [CB-Test_CHxx],
[DS11-Test_CHxx], [DS12-Test_CHxx], [DS13-Test_CHxx], and [DS21-Test_CHxx].
Test for BI and BO circuits
13.4.3
Binary input circuit test (SLOT*BIxx-SET)
(i)
Setting [SLOT*-BIxx-SET] allows to have a virtual input at a binary input circuit.
Binary output circuit test (SLOT*BOxx-SET)
(ii)
Setting [SLOT*-BIxx-SET] allows to have a virtual output at a binary input circuit.
Note: For the BI and BO test operation, see Chapter
separately.
Test for mode change (MDCTRL)
13.4.4
The function is provided to detect a test mode. For more information, see Chapter
control function: Mode control function
Signal monitor
13.4.5
The function is provided in order that the user can observe IED internal signals. For more
information, see Chapter
separately.
Communication protocol: IEC 61850 communication
).
Automatic supervision function
, separately.
Technical description: Human machine interface: Monitoring jacks
- 720 -
.
User interface: Test sub-menu
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
6F2S1931 (0.20)
.
,
General
,