Setting for the report (Dead band feature)
The data collected in the metering function will be sent to the network upward, but the data
sent may give the network a heavy burden because the amount of the data sent could be larger.
Thus, the dead band (SD) feature is designed not to report data unnecessary (say, the dead
band feature regulates not to send the same data repeatedly). In practice the analog values in
the metering function are not always the same. The user can make rules not to send data
always using % settings.
For example when 1A rated current is employed, and setting [ISD] has a default setting value
5.00, data will be reported when the present current value is changed beyond ±0.05A (i.e.,
5.00% of the rated 1A current).
Table 8.5-1 shows respective settings for the power quantities.
Table 8.5-1 SD settings for respective quantities
Quantities
Voltage
Current
Frequencty
Figure 8.5-1 Metering setting in the setting screen
Note: For the operation of the menu, see Chapter
Units for
SD settings
settings
%
VSD
%
ISD
%
FSD
Metering
10:48
1/3
ISD
+
5.00 %
VSD
+
0.60 %
FSD
+
0.60 %
- 427 -
6F2S1931 (0.20)
Setting ranges
0.00% to 50.00%
0.00% to 50.00%
0.00% to 50.00%
User interface: Setting sub-menu
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
.