relay. If the setting value (signal No.) is "0", all setting items related events are disable and
the frame is not provided.
†Note: A relevant Data ID is required to select; the description is obtained
automatically.
Type ID
Type ID=1 (Time-tagged message) or Type ID=2 (Time-tagged message with relative time)
is selected to set the frame type. It is recommended that the frame related to status is set
to Type ID=1 and the frame related to faults is set to Type ID=2. In Type ID=2, the trigger
signal for the relative time should be set. For the setting, see Section 10.4.5(i).
INF
Information number (INF) of the frame is set. The INF can be set to 0 to 255. When the
standard frame is provided, the INF according to the Appendix† is recommended. If the
frame out of standard is provided, the INF should be set referring Table 10.4-5 and the
Appendix†.
Table 10.4-5
†Note: See
Appendix: IEC 60870-5-103 interoperability: Semantics of Information
number.
FUN
Function type (FUN) is set referring to Table 10.4-6. The FUN can be set to 0 to 255. When
clicking the "Change all FUNs" on the Common setting screen, all FUNs are changed to the
setting values at Common setting.
Table 10.4-6
INF category of Monitor direction
INF
0 to 15
system functions
16 to 31
Status
32 to 47
Supervision
48 to 63
earth fault
64 to 127
short circuit
128 to 143
auto-reclosure
144 to 159
Measurands
160 to 239
not used
240 to 255
generic functions
Semantics of Function type
0 - 127
private range
128
distance protection
129
not used
144
not used
145
not used
160
overcurrent protection
161
not used
176
transformer differential protection
177
not used
192
Line differential protection
- 603 -
Category
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
6F2S1931 (0.20)