DISTURB_REC (Function ID: 204001)
Setting items
Record Time
Pre-fault Time
Sampling Rate
Interpolate Mode
Trip Trig.SW
Binary Signal1
Binary Sig.Name1
Binary Signal2
Binary Sig.Name2
Binary Signal3
Binary Sig.Name3
......
......
Binary Signal256
Binary Sig.Name256
CBP_DRT(Function ID: 4B3001)
Setting items
OC-DRT-EN_1
CH1
OC-DRT_1
OC-DRT-EN_2
CH2
OC-DRT_2
OC-DRT-EN_3
CH3
OC-DRT_3
~
OC-DRT-EN_24
CH24
OC-DRT_24
Range
0.1 - 10.0
0.1 - 10.0
7.5 / 15
On / Off
Off / On
(Preferred DataID)
(Preferred name)
(Preferred DataID)
(Preferred name)
(Preferred DataID)
(Preferred name)
......
......
(Preferred DataID)
(Preferred name)
Range
Off / On
0.10 - 50.00
0.50 - 250.00
Off / On
0.10 - 50.00
0.50 - 250.00
Off / On
0.10 - 50.00
0.50 - 250.00
~
Off / On
0.10 - 50.00
0.50 - 250.00
Contents
Unit
s Time for disturbance recording
s Pre-fault time
deg Sampling rate in electrical degree
– Generating interpolations in 15 deg.
– Operation with the TRC trip command
– Logic signal1 for the operation
– Name of the logic signal1
– Logic signal2 for the operation
– Name of the logic signal2
– Logic signal3 for the operation
– Name of the logic signal3
– ......
– ......
– Mode setting for the detection
– Name of the trigger signal768
Contents
Unit
Enabling Overcurrent relay to record in CH1
A
Operating threshold of OC-DRT relay in CH1
Enabling Overcurrent relay to record in CH2
A
Operating threshold of OC-DRT relay in CH2
Enabling Overcurrent relay to record in CH3
A
Operating threshold of OC-DRT relay in CH3
~
Enabling Overcurrent relay to record in CH24
A
Operating threshold of OC-DRT relay in CH24
- 381 -
6F2S1931 (0.20)
Default
Note
3.0
0.3
15
Off
On
See Setting
table in this
section
Default
Note
Off
1.00
5.00
Off
1.00
5.00
Off
1.00
5.00
~
Off
1.00
5.00
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)