Toshiba GR200 Series Instruction Manual page 654

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

[Type3] Mapping about Input register type
Figure 10.5-24 illustrates a mapping example for the Modbus Input register. In the figure, a
signal (Data ID) of the TCPIP_DRV function are mapped for the Modbus address
Modbus screen in Simple mode
The Input register type is Read-Only mode.
Modbus address: 10000
IED Data ID (FID: 230201)
2
3110101001
RX1_CNT
Data length of the RX1_CNT is 16-bits type.
Signal monitoring point (Data ID)
Figure 10.5-24 Example setting of Modbus Input register
Note: Addresses from 10000 —10999 are designed for 8-bits or 16-bits data length (see
2
Table 10.5-2).
Read Input register
- 640 -
6F2S1931 (0.20)
Dropped
IED output point
Dragged
IED signals (Data IDs)
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
(10000).
1