Toshiba GR200 Series Instruction Manual page 235

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Input
Command "Remote-Reset-Control"
540001 700E016D09
GCNT01_CMM_REQ
Either "SBO mode" or "DIR mode"
(e.g., "ctlmodel" in IEC61850*)
Logic '0' signal (Always Low (FALSE))
‡Note: A "select condition" signal is provided from the select condition logic. For more
information, see Figure 3.7-7.
*Note: The GNCT01 function can run in either the "SBO mode" or the "DIR mode" using
a signal called "ctlmodel" when communication is implemented using IEC61850.
To use this signal, the user should map it for IEC61850 communication.
Note: To identify the input and output points of the other GCNT02–GCNT32 logics, see
††
Table 3.7-2 for the inputs and Table 3.7-5 for the outputs.
GCNT01 function (Function ID: 54001)
For SBO operation
Select command
For DIR operation
Operate command
In SBO operate
In DIR operate
Select condition‡
Figure 3.7-6 Select 'Reset' in GCNT01
- 221 -
Select logic in GCNT01
1≥
&
&
††
Centralized GRB200
6F2S1931 (0.20)
Output
&
To "Wait for a next
command"
To BO connection
"GCNT01_SLD_CSCN"
(540001 8A0E011E76)
0
t
Complete
0.2s
To "Wait for a command"
"GCNT01_SLF_CSCN"
(540001 8B0E011E7B)
0
t
Select "Failed"
0.3s
(Soft: 030, 031, 032, 033, 034)