Toshiba GR200 Series Instruction Manual page 365

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

communication function (CBP_COMRCV_MU (Function ID: 4F2A01)).
‡Note: 64 logical signals are selectable for recording. For example in this purpose, the
user may choose an operation signal on the circuits of the BIO modules (BIOs).
Fault quantities and pre-fault-quantities
(iv)
Quantities that amplitude and phase angle of voltage and current—are memorized in the fault
recorder, as shown in Table 7.1-1. Items, pre-fault quantities just before a fault (i.e., tripping),
are also captured and memorized. Default 10 seconds has been set for setting [Pre-Fault time],
but it is possible to change it to memory the times longer.
Table 7.1-1 Recording quantities at a fault ant before the fault
Abbreviations
DIFCH: Ida, Idb, Idc
DIFZA:
IdaA, IdbA, IdcA
DIFZB:
IdaB, IdbB, IdcB
DIFZC:
IdaC, IdbC, IdcC
DIFCH: Ira, Irb, Irc
DIFZA:
IraA, IrbA, IrcA
DIFZB:
IraB, IrbB, IrcB
DIFZC:
IraC, IrbC, IrcC
ZoneA:
VaA, VbA, VcA / VabA, VbcA, VcaA
ZoneB:
VaB, VbB, VcB / VabB, VbcB, VcaB
ZoneC:
VaC, VbC, VcC / VabC, VbcC, VcaC
ZoneA:
V1A, V2A, V0A
ZoneB:
V1B, V2B, V0B
ZoneC:
V1C, V2C, V0C
Respective CHs:
Ia, Ib, Ic
Screen information
7.1.2
Figure 7.1-1 illustrates the information displayed on the IED screen†, which can display up to
eight fault records (#1 to #8). Figure 7.1-2 illustrates the structure of the first fault record#1.
DIFZD:
IdaD, IdbD, IdcD
DIFZE:
IdaE, IdbE, IdcE
DIFZF:
IdaF, IdbF, IdcF
DIFZD:
IraD, IrbD, IrcD
DIFZE:
IraE, IrbE, IrcE
DIFZF:
IraF, IrbF, IrcF
ZoneD:
VaD, VbD, VcD / VabD, VbcD, VcaD
ZoneE:
VaE, VbE, VcE / VabE, VbcE, VcaE
ZoneF:
VaF, VbF, VcF / VabF, VbcF, VcaF
ZoneD:
V1D, V2D, V0D
ZoneE:
V1E, V2E, V0E
ZoneF:
V1F, V2F, V0F
- 351 -
6F2S1931 (0.20)
Displayed quantities
Magnitude of phase
differential current (Id) of
Check-zone-relay (DIFCH)
and Discriminating-zone-
relays (DIFZA to DIFZF)
Magnitude of restraint current
(Ir) of Check-zone-relay
(DIFCH)
and Discriminating-zone-relays
(DIFZA to DIFZF)
Magnitude and phase angle of
phase and phase-to-phase
voltage (V) in each zone
Magnitude and phase angle of
symmetrical component
voltages (V1, V2, and V0) in
each zone
Magnitude and phase angle of
phase currents (Ia, Ib, Ic) in
each CH
Centralized GRB200