Figure 4-3.
Problems with
communications flowchart
See "PlantWeb™ Alerts" on page 4-7
Perform Recommended
Action, see Table 4-13 on
Yes
page 4-28.
Read the following parameters in the
Resource Block to determine the
recommended action.
BLOCK_ERR (see Table 4-3)
SUMMARY_STATUS (see Table 4-4)
DETAILED_STATUS (see Table 4-5)
Yes
Perform Recommended
Action, see Table 4-5.
COMMUNICATIONS ESTABLISHED BUT HAVE
"BLOCK_ERR" OR AN "ALARM" CONDITION.
Problem Identified?
No
Problem Identified?
No
For more detailed
information
Perform the following steps in the Sensor
Transducer Block to determine the
recommended action.
BLOCK_ERR (see Table 4-6)
XD_ERR (see Table 4-7)
DETAILED_STATUS (see Table 4-8)
RECOMMENDED_ACTION (see Table 4-8)
SENSOR_DETAILED STATUS (see Table 4-8)
Problem Identified?
Yes
Perform Recommended
Action, see Table 4-8.
Rosemount 3144P
If error condition does not exist
in the Resource Block then it is a
configuration problem, see "AI
BLOCK_ERR Conditions." in
Table 4-10
Yes
Perform Recommended
Action, see Table 4-11.
No
Problem Identified?
No
If the problem persists
contact your local
Rosemount representative.