Manual Supplement
00809-0400-2410, Rev AA
1.2

Electrical installation

1.2.1
Rosemount 2410 Tank Hub connections
Figure 1-4. Terminal Block in the Explosion-Proof/Flameproof Compartment
Table 1-2. Terminal Assignment for Non-Intrinsically Safe Side
Terminal
1
2
3
4
5
6
7a/7b
8a/8b
9
10
11
12
PE
GND_1
GND_2
Rosemount 2410 Tank Hub
Primary field bus
Designation
Function
N / -
Power, Neutral / DC -
L / +
Power, Line / DC +
K1 A
Relay 1 output (optional). Hardware configurable NO/NC.
K1 com
Relay 1 common
K2 A
Relay 2 output (optional). Hardware configurable NO/NC.
K2 com
Relay 2 common
P Bus B
Primary communication bus B
P Bus A
Primary communication bus A
S Pwr -
Secondary bus power - (optional)
S Pwr +
Secondary bus power +(optional)
S Bus B
Secondary communication bus - (optional)
S Bus A
Secondary communication bus + (optional)
PE
Power supply protective ground
GND_1
Housing chassis/shield Primary bus
GND_2
Housing chassis/shield Secondary bus
Rosemount 2410 Tank Hub
Secondary field bus
March 2016
5