7.
a.
b. Enter the Unit ID and select the new Modbus Address.
c.
d. In the 2410 Tank Hub Communication window select Verify Communication to
8.
9.
1.3.3
Configure specific variables for Enraf
1.
10
Default Modbus Address is 247 for the tank hub. It is recommended to change it to
an address 101-199. Do the following:
In the 2410 Tank Hub Communication window select Change Address on Device...
to open the Change Address window.
When changing the device address, the Unit Id is used as a unique identifier of the
device. The Unit Id can be found on a label mounted on the device.
Select OK to confirm the address settings and close the Change Address window.
check that communication is established between the TankMaster work station
and the tank hub. The Unit ID will appear when TankMaster finds the tank hub.
In the 2410 Tank Hub Communication window select Next to continue the
installation procedure of the tank hub.
Continue configuration as usual for a tank hub installation.
In the Configuration tab, select Enraf Emulation.
Manual Supplement
00809-0400-2410, Rev AA
Rosemount 2410 Tank Hub