Serial Option Port 1 (Ex) - Omron SYSMAC CP Series User Manual

Hide thumbs Also See for SYSMAC CP Series:
Table of Contents

Advertisement

7-2-6

Serial Option Port 1 (EX)

The settings are applicable to the N
2 ports is mounted.
Since this setting is reflected by power OFF and ON, the PLC Setup and the actual operation settings-
may be different. The actual operation settings can be confirmed in words A616.
Communications Settings
Name
1
Communications Settings
2
Mode
(When custom settings have been
selected.)
2-1
RS-232C (No-protocol) Settings
2-1-1
Baud
2-1-2
Format
(data length, stop bits,
parity)
2-1-3
Start Code
2-1-4
Start Code (setting)
2-1-5
End Code
CP2E CPU Unit Software User's Manual(W614)
-type CPU Units when Serial Option Board CP2W-CIFD
Default
Possible settings
Standard (9600;
Standard
1, 7, 2, E)
Baud rate: 9,600 bps
(Default settings)
Start bits: 1 bit
Data length: 7 bits
Parity: Even
Stop bits: 2 bits
Custom
RS-232C (No-protocol)
RS-232C (No-protocol)
PC Link (Slave)
PC Link (Master)
Modbus-RTU Easy Master
Modbus RTU Slave
9,600 bps
1,200 bps
2,400 bps
4,800 bps
9,600 bps
19,200 bps
38,400 bps
57,600 bps
115,200 bps
7 bits, 2 bits, even
7 bits, 2 bits, even
7 bits, 2 bits, odd
7 bits, 2 bits, no parity
7 bits, 1 bit, even
7 bits, 1 bit, odd
7 bits, 1 bit, no parity
8 bits, 2 bits, even
8 bits, 2 bits, odd
8 bits, 2 bits, no parity
8 bits, 1 bit, even
8 bits, 1 bit, odd
8 bits, 1 bit, no parity
Disable.
Disable.
Set.
00 Hex
00 Hex
:
FF hex
None
Received Bytes (no end code)
(Received Bytes)
CR, LF
Set End Code
7 PLC Setup
with
When setting is read by
CPU Unit
When power is turned ON
When power is turned ON
When power is turned ON
When power is turned ON
When power is turned ON
When power is turned ON
When power is turned ON
7-13
7

Advertisement

Table of Contents
loading

Table of Contents