9
8 Segment & 4x16 Segment Programmable Models w/OTP
Programming the Controller
StEP
To climb instantaneously from the current temperature to a specified temperature.
1. Press the PAGE button until you reach the program list (ProG LiSt).
2. Press the SCROLL button until display reads, tYPE."
3. Press the UP or DOWN button until the display reads, "StEP."
4. Press the SCROLL button until display reads, "tGt."
5. Press the UP or DOWN button to set a target setpoint.
cALL (Running Multiple Programs; 4x16 Segment Programmable Models Only)
To call a program as a subroutine:
If you want to run multiple programs, you can program the controller to "call" or link one program to
another. This makes it possible to run one program at any time during another program and also
return to the original program if desired.
1. Press the PAGE button until you reach the program list (ProG LiSt).
2. Press the SCROLL button until display reads, "tYPE."
3. Press the UP or DOWN button until display reads, "cALL."
4. Press the SCROLL button until display reads, "PrG.n."
5. Press the UP or DOWN button to select a program number to be linked.
6. Press the SCROLL button until display reads, "CYC.n."
7. Press the UP or DOWN button to select the number of cycles the linked program is to be run.