General Vent Installation; Installation Of Side Wall Venting - Kingsman marquis ENCLAVE MQVLB48NE2 Installation Instructions Manual

Table of Contents

Advertisement

This gas appliance is approved to be vented either through the side wall or vertically through the roof. Only Kingsman Flex (Z-Flex) Venting Kits and
components specifically approved and LABELED for this stove may be used. This appliance is also approved for use with 5 x 8 M&G-Duravent Direct
Vent system (Model DV-GS Series) and Snorkel, BDM Pro Form Direct Vent, Ameri-Vent
Direct Vent Pipe System, ICC Excel Direct, Metal Fab Sure-Seal DV and Selkirk Direct Temp.
RIGID OR HARD PIPE
Follow installation instructions provided by M&G-Duravent/Ameri-Vent/Selkirk Direct Temp,
ICC Excel Direct, and Metal Fab Sure-Seal DV for installation of pipe and adhere to the
clearance to combustibles provided in this manual. Apply a bead of Mill Pac high temp sealant
to all joints of pipes, adapters and termination, when using Kingsman Flex (Z-Flex) venting
and M&G-Duravent venting.
FLEX PIPE VENTING
Kingsman Flex pipe is shipped in unexpanded length. When installing pipe expand the lengths.
Pipe can be expanded to twice their lengths e.g. 4ft to 8ft. Fully expand pipe and cut off excess.
Do not use more than 2 couplers (Order ZDV5FC & ZDV8FC – DO NOT fabricate couplers)
to extend short pipes. Single sections are preferred in an installation attaching at the fireplace
and termination.
Place the spring spaces provided approximately every two feet to stabilize 5" flex in the center
of 8" flex. When forming bends place spring in bend or before and after. (See Fig. 1). Horizontal
runs require support metal straps every 2 feet. In offset installation support straps should be
used to stabilize pipe.
Expand 5" and 8" flex pipe to the point that the 8" protrudes approximately 2 to 3 inches past
outer wall and the 5" flex protrudes approximately 2 to 3 inches past the 8" flex. (See Fig. 1).
Attach the 5" pipe to the termination first and secure with sealant and screws then attach the 8"
flex to the termination with caulking and screws. Termination may then be moved back to the
outer wall and attached to home screwing into the framing. Silicone around termination to
waterproof. If siding shield is going to be used attach this using same attaching hole as the top
of termination after termination has been caulked for water proofing.
Use Hi Temp Sealant
Apply a bead of Mill Pac high temp sealant to all joints and use four screws to secure each
pipe at fireplace, termination and any joint if joining any sections of pipe.
WARNING: DO NOT mix parts from different systems unless stated in the manual.
1.
To determine the minimum distance from the bottom of fireplace to center of vent see the Framing Your Gas Fireplace section. Cut a hole
through the wall allowing for a 12" x 12" (inside diameter) in combustible walls for wall thimble or a 9" diameter hole in a non-combustible wall
(See Figure 2).
2.
For the clearance to combustible above a 90 degree bend see Clearance
to Combustibles section.
3.
Select the approximate vent length, precise measurements are not needed
as your flex pipe can be expanded to twice its s
4.
hipped length for ease of installation
5.
To install wall thimble center over 12" x 12" (inch) framing from both sides
of wall and secure. Route flex vent pipe through wall thimble (See Figure
1).
6.
Before joining pipes, apply a bead of high temperature sealant (Mill Pac) to
end of pipe. First attach the five inch (5") flue pipe to the vent termination
with sealant, and secure with the four screws provided. At this time make
sure the spacer springs are attached to the (5") flex pipe as required. Then
attach the eight inch (8") pipe by the same method.
7.
Mount vent termination and seal to wall using caulking around the wall
thimble to weather proof. After installing the vent termination, double check
to make sure the pipe extends properly through wall thimble and into vent
termination.
8.
Before joining pipes to fireplace flue, apply a bead of high temperature
sealant (Mill Pac) to end of pipe. First attach the five inch (5") flue pipe to
fireplace with sealant, and secure with the four screws provided. At this
time verify that the spacer springs are attached properly to the (5") flex pipe
as required. Then attach the eight inch (8") pipe by the same method.
9.
Support horizontal pipes every two (2) feet (61 cm) with metal strap bands.
Re-check fireplace to make sure it is level and properly positioned and
secured.
10. Support vertical pipes to maintain a minimum of 1" or greater clearance to
combustibles with metal strapping bands.
11. If finishing the outside wall with vinyl or wood siding it is recommended that
a Siding Shield be installed, Part Number ZDVSSLR.
Note: Vent Termination must not be recessed into wall or siding.
General Vent Installation Information

Installation of Side Wall Venting

FRAMING DIMENSION
Combustible Wall
Cut a 12" hole through exterior wall and frame as
shown below.
Non Combustible Wall
Cut or drill 9" diameter hole.
NOTE: It is critical to the proper and safe operation of
this fireplace that on all connections the inner liner and
the outer casing are both caulked with liberal amounts
of sealant. Do not use any kind of tape or silicone other
than that recommended in this manu
MINIMUM 1" TO
COMBUSTIBLES
COMBUSTIBLE AIR INLET
FLUE GAS OUTLET
MIN 57-1/2"
FIGURE 1
12"
12"
THROUGH COMBUSTIBLE
WALL
WARNING: A HORIZONTAL VENT CERTIFIED
GUARD (SAFETY CAGE) IS AVAILABLE WHEN
REQUIRED BY LOCAL CODES.
al, Mill Pac Sealant
FRAMING DETAIL
9" DIA
MIN 57-1/2"
THROUGH NON-
COMBUSTIBLE WALL
FIGURE 2
67