S+S Regeltechnik Rymaskon 600 Operating Instructions Manual page 42

Room control unit with colour touch screen, with bacnet or modbus connection
Table of Contents

Advertisement

Operating instructions
RYMASKON
®
600 - BACnet
RYMASKON 600 Series | Parameter Table | Last Updated: 23/03/2022 (EN)
RYMASKON
®
600 - Modbus
FAN, BOOST, LIGHTS AND BLINDS
Parameter name
Light Interlock
ALARMS
Parameter name
Alarm 1 Source
Alarm 1 Amber Threshold
Alarm 1 Red Threshold
Alarm 1 Hysteresis
Alarm 2 Source
Alarm 2 Amber Threshold
Alarm 2 Red Threshold
Alarm 2 Hysteresis
SYSTEM
Parameter name
Address
Baud rate
Parity
Stop Bits
S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de
Description
Locks the lighting
(1) Disabled
Light intensity is maintained when toggling between
comfort (standard mode) and ECO/OFF
(2) Comfort
• ECO/OFF à Comfort (standard mode):
Light intensity 100%
• Comfort (standard mode) à ECO/OFF:
Light intensity 0%
• Priority switching by hand or via the bus;
maintained in ECO/OFF mode
(3) Comfort + ECO
• ECO/OFF à Comfort (standard mode):
Light intensity 100%
• Comfort (standard mode) à OFF:
Light intensity 0%
• Comfort (standard mode) à ECO:
Light intensity remains unchanged
• Priority switching by hand or via the bus;
maintained in ECO/OFF mode
(see chapter "Blind and Light icons")
Description
Source for alarm indicator, alarm 1
Switching point for amber alarm indicator, alarm 1
Switching point for red alarm indicator, alarm 1
Hysteresis for alarm 1
Source for alarm indicator, alarm 1
Switching point for amber alarm indicator, alarm 1
Switching point for red alarm indicator, alarm 1
Hysteresis for alarm 2
Description
Configuring the bus address
Baud rate for Modbus or BACnet units
Parity for Modbus or BACnet units
Stop bits for Modbus or BACnet units
Range
0 = Disabled (Default)
1 = Comfort
2 = Comfort + ECO
Range
0 = CO2 sensor
1 = Room (Temperature)
2 = Humidity
3 = None (Default)
0...5000 (default 0)
0...5000 (default 0)
0...5000 (default 0)
0 = CO2 sensor
1 = Room (Temperature)
2 = Humidity
3 = None (Default)
0...5000 (Default 0)
0...5000 (Default 0)
0...5000 (Default 0)
Range
Modbus: 0...247 (Default 1)
BACNet: 0...127 (Default 1)
0 = 9600 (Default)
1 = 19200
2 = 38400
3 = 57600
4 = 76800
0 = None (Default)
1 = Odd
2 = Even
0 = 1 Stop Bit (Default)
1 = 2 Stop Bits
42