Analogue Outputs - S+S Regeltechnik Rymaskon 600 Operating Instructions Manual

Room control unit with colour touch screen, with bacnet or modbus connection
Table of Contents

Advertisement

Operating instructions
RYMASKON
®
600 - BACnet
RYMASKON
®
600 - Modbus
MODES FOR

ANALOGUE OUTPUTS

S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de
The controller has three analogue outputs (0...10 V DC) and they are typically linked to the control circuit outputs.
The following configuration options are available:
• Bus
Operated as 0...10 V output variable for the bus
• Heating stage 1 (Htg Stage 1)
The 0...10 V output is linked to heating stage 1 (default: Y2)
• Heating stage 2 (Htg Stage 2)
The 0...10 V output is linked to heating stage 2
• Cooling stage 1 (Clg Stage 1)
The 0...10 V output is linked to cooling stage 1 (default: Y3)
• Cooling stage 2 (Clg Stage 2)
The 0...10 V output is linked to cooling stage 2
• Fan (Modulating Fan)
The 0...10 V output is linked to the fan control circuit output (default: Y1)
• CO2 control (CO2)
The 0...10 V output is linked to the CO2 control circuit outputs
(see chapter "CO2 control circuit")
• Max. VAV (Max. Clg/CO2)
The 0...10 V output is linked to the maximum capacity of the control circuits for cooling stage 1 and CO2
(see chapter "Fan speed control" and "CO2 control circuit")
• Max. Fan (Max. Fan/CO2)
The 0...10 V output is linked to the maximum capacity of the control circuits for CO2 and blower
(see chapter "CO2 control circuit")
• Humidification
The 0...10 V output is linked to the control circuit output for humidification
(see chapter "Humidity control circuit")
• De-humidification
The 0...10 V output is linked to the control circuit output for de-humidification
(see chapter "Humidity control circuit")
• Light
0...10 V linked to lighting stage
• Blind 1 Level
0...10 V linked to blind 1 position
• Blind 1 Tilt
0...10 V linked to the blind 1 slats' angle of inclination
• Blind 2 Level
0...10 V linked to blind 2 position
• Blind 2 Tilt
0...10 V linked to blind 2 slats' angle of inclination
• Amber/red alarm
0...10 V is at 50 % if the amber or the red alarm is active
• Red alarm (Red)
0...10 V is at 100 % if the red alarm is active
• Heating stage 1 static (Htg Stage1 Stat)
(see chapter "Relay output/ON-OFF")
• Cooling stage 1 static (Clg Stage1 Stat)
(see chapter "Relay output/ON-OFF")
• Fan static (Fan Stat)
(see chapter "Relay output/ON-OFF")
• AUX control circuit (Aux. Loop)
(see chapter "AUX control circuit")
• 6-way valve (6-Port)
(see chapter "6-way valve control")
• 6-way valve inverse (6-Port Reverse)
(see chapter "6-way valve control", inverse mode).