User Interface - S+S Regeltechnik Rymaskon 600 Operating Instructions Manual

Room control unit with colour touch screen, with bacnet or modbus connection
Table of Contents

Advertisement

Operating instructions
RYMASKON
®
600 - BACnet
RYMASKON
®
600 - Modbus

USER INTERFACE

Screens, lighting
and calibration
S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de
The following diagrams are typical display options for the RYMASKON
The multi-colour LCD touch display facilitates making the required settings
and visualises the actual state of the controlled system with easily understandable icons.
MAIN SCREEN
°C
Blind 1 Blind 2
21
°C
.
0
A
Room
23
°C
.5
Fig. 1a Main screen
The small action circle (grey) alternately displays the current sensor values (if enabled).
The large setpoint ring illustrates the heating or cooling consumption (red/blue).
If temperature control is in the "dead zone", the ring is white.
The colour intensity changes depending on the difference between the actual temperature and
the currently controlled heating/cooling temperature (setpoint). From a delta of 2°C (3.6°F) or more,
the entire ring is red/blue.
ENERGY RING COLOURS
-
HDz - 2°/ 3.6°F
HDz
calcSP
Deadzone
Screen backlighting (standby)
If the display of the main screen is not touched for 30 sec., the display will be dimmed to the configured
standby value (default 5/max. 20).
Use the settings to adjust the brightness of the touch display
(System – Brightness). If this value is configured to 0, the display is completely dark when it is inactive.
Touch the display to automatically re-enable the backlighting.
Tap the
icon on the main screen to immediately dim the display to the set value.
Tap the icon again in standby to completely switch off backlighting.
Screen calibration
The touch display can be re-calibrated during a unit reset.
The unit performs the following two types of resets:
1. When the unit starts up (power supply present)
2. After completing parameter configuration in setting mode and returning to the main screen.
During reset (dark screen), swipe in the direction of all four edges of the display and then follow the
instructions. Confirm recalibration with "OK".
11
AUXILIARY SCREEN
Fig. 1b Auxiliary screen
(opens by tapping the grey action circle
on the main screen)
+
CDz
CDz + 2° / 3.6°F
MEASURED
TEMPERATURE
®
600 controller.
BLIND SCREEN
Blind 1
Fig. 1c Blind screen
(opens by tapping the Blind icon
on the main screen)