Operating instructions
RYMASKON
®
600 - BACnet
RYMASKON
®
600 - Modbus
INSTALLATION AND
COMMISSIONING

IMPORTANT NOTES

S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de
Commissioning is mandatory and may only be performed by qualified personnel! Please read these instruc-
tions prior to installation and commissioning, and comply with the specifications that they contain!
Mounting shall take place while observing all relevant regulations and standards applicable for the place of
measurement (e.g. such as welding instructions, etc.). It is particularly important to comply with the
following:
- VDE ⁄ VDI technical temperature measurements, directives, measurement set-ups for
temperature measurements.
- EMC directives
- It is imperative to avoid parallel routing of current-carrying lines
- We recommend the use of shielded cables with the shielding attached to the DDC/PLC at one side.
Before mounting, make sure that the existing technical parameters of the measuring instrument comply
with the actual conditions at the place of utilization, particularly with regard to:
- the measuring range
- the maximum permissible temperature and humidity
- the protection type and protection class
- oscillation, vibration and impacts must be avoided (< 0.5 g)
Devices with integrated CO2-Sensor
Devices with integrated CO2-Sensor have an automatic calibration of the carbon dioxide measurement –
ABC logic. The Automatic Background Logic is a self-calibrating mechanism that is suitable for use in
applications in which the CO2 concentration regularly drops to fresh air level (350 - 500 ppm).
This should typically happen at times during which the rooms are unoccupied.
The sensor reaches its normal accuracy after 24 hours of continuous operation in an environment which
has been exposed to a fresh air supply of 400 ppm CO2. The deviation error remains minimal with at least
4 cases of sensor exposure to fresh air within 21 days. The ABC logic requires continuous operating
cycles of longer than 24 hours in order to function properly.
Only the valid edition of our conditions and the valid "General Conditions for the Supply of
Products and Services of the Electrical and Electronics Industry" (ZVEI conditions) and
the supplementary clause "Extended Retention of Title" apply as the terms and conditions
regulating this purchase.
The following points must also be complied with:
- These instructions must be read before installation and commissioning,
and all of the specifications that they contain must be complied with.
- The units must only be connected to an extra-low safety voltage in a de-energised condition.
Use shielded cables to avoid damage to the unit and faults (e.g. resulting from voltage induction),
avoid parallel routing with live lines, and comply with the EMC directives.
- This unit must only be used for its intended purpose, whereby the applicable VDE safety regulations and
all regulations issued by the regional and national regulatory authorities, TÜV and local energy providers
must be complied with. The purchaser must ensure that the relevant building and safety regulations are
complied with, and must avoid hazards of all kinds.
- No warranty or liability whatsoever will be accepted for defects and damage arising from improper
use of this unit.
- The warranty and liability excludes consequential damage caused by a fault in this unit.
- The units must only be installed and commissioned by qualified personnel.
- Only the technical data and connecting conditions specified by the installation and operating instructions
which are included in the scope of delivery of the unit apply. Deviations from the depictions contained in
the catalogue are not additionally listed, and are possible as a result of technical progress and the
continuous improvement of our products.
- Any alterations made to the unit by the user will void the warranty.
- This unit must not be installed close to sources of heat (e.g. radiators) or their heat flow. Avoid direct
solar irradiation or heat radiation from similar sources (powerful lamps, halogen spotlights).
- Operating this unit close to other devices that do not comply with EMC directives may influence the
functionality thereof.
- This unit must not be used for monitoring purposes which serve the purpose of protecting persons
against hazards or injury, as an Emergency Stop switch on systems or machinery, or for any other
similar safety-related purposes.
- The housing dimensions and the dimensions of accessories may differ slightly from the specifications
of these instructions.
- Changes to these documents are not permitted
- In cases of complaint, we will only accept complete units returned in their original packaging.
2