S+S Regeltechnik Rymaskon 600 Operating Instructions Manual page 38

Room control unit with colour touch screen, with bacnet or modbus connection
Table of Contents

Advertisement

Operating instructions
RYMASKON
®
600 - BACnet
RYMASKON 600 Series | Parameter Table | Last Updated: 23/03/2022 (EN)
RYMASKON
®
600 - Modbus
INPUTS AND OUTPUTS
Parameter name
Humidity Display
CO2 Display
Aux. Loop Source
Aux temperature control
circuit source
Digital Input Mode
Digital Input Delay
RI1 mode
RI2 Mode
Internal Sensor Cal.
Integrated sensor calibration
RI1 Cal.
RI1 calibration
RI2 Cal.
RI2 calibration
CO2 Cal.
CO2 calibration
Humidity Cal.
Humidity calibration
S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de
Description
Release of the humidity display
(for units with RH option)
The value is shown in the small action circle.
Release of the CO2 display (for units with CO2 option)
The value is shown in the small action circle.
Source of the temperature measurement for the auxiliary
control circuit. (Display in the small action circle when
recording a valid temperature value.)
Operating mode of the digital input (DI mode)
Delay time of the digital inputs
(when switching from active to inactive)
Operating mode of input RI1/AI1
(see chapter "Modes for inputs RI1 and RI2")
Operating mode of input RI2/AI2
(see chapter "Modes for inputs RI1 and RI2")
1-point compensation for integrated temperature sensor
1-point compensation for temperature sensor on RI1
(NTC10K)
1-point compensation for temperature sensor on RI2
(NTC10K)
1-point compensation of the integrated CO2 sensor
(Units with CO2 option)
1-point compensation of the humidity sensor
(Units with RH option)
Range
0 = Disabled
1 = Enabled (Default)
0 = Disabled (Default)
1 = Enabled
0 =Built-In Sensor (Default)
1 = Network Temp
0 = Close for ECO (Default)
1 = Open for ECO
2 = Close for OFF
3 = Open for OFF
4 = Change-Over
5 = Disable Cooling
6 = DI Contact Alarm
7 = Network
8 = Close for Boost
9 = Open for Boost
0...28800s (default 0s)
0 = Disabled (default)
1 = Room
2 = Floor
3 = Aux. Loop
4 = Heating/Cooling
5 = Network NTC10 (bus)
6 = Network 0–10V (bus)
7 = CO2
8 = Main Loop (main control
9 = Close for ECO (DI-mode)
10 = Open for ECO (DI-mode)
11 = Close for OFF (DI-mode)
12 = Open for OFF (DI-mode)
13 = Condensation (condensation
14 = Network DI (Bus DI)
-10.0...+10.0°C/°F
-10.0...+10.0°C/°F
-10.0...+10.0°C/°F
-500...+500ppm
-10.0...+10.0% RH
38
(heating/cooling, changeover)
circuit)