Version: 10.10.2022 / TH
RYMASKON
Modbus Slave User Manual
User Manual
for Room Control Units
®
RYMASKON
211-Modbus
®
RYMASKON
212-Modbus
®
RYMASKON
221-Modbus
®
RYMASKON
222-Modbus
®
RYMASKON
231-Modbus
®
RYMASKON
232-Modbus
®
RYMASKON
241-Modbus
®
RYMASKON
242-Modbus
®
RYMASKON
251-Modbus
®
RYMASKON
252-Modbus
®
RYMASKON
261-Modbus
®
RYMASKON
262-Modbus
© S+S REGELTECHNIK GMBH | PIRANER STR. 20 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |
®
200-Modbus
Page 1 of 55
www.SplusS.de

Advertisement

Table of Contents
loading

Summary of Contents for S+S Regeltechnik RYMASKON 200-Modbus

  • Page 1 RYMASKON 241-Modbus ® RYMASKON 242-Modbus ® RYMASKON 251-Modbus ® RYMASKON 252-Modbus ® RYMASKON 261-Modbus ® RYMASKON 262-Modbus © S+S REGELTECHNIK GMBH | PIRANER STR. 20 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 | www.SplusS.de Page 1 of 55...
  • Page 2 All Text and Data supplied within this manual are subjects to copyright protection. Without the express written explicit approval of S+S Regeltechnik GmbH no part of this work may be copied or distributed for any purpose, regardless in which way or by which means, electronically or mechanically.
  • Page 3: Table Of Contents

    Troubleshooting ................................ 53 6.1. Technical Support ..................... 53 Specifications ................................54 7.1. Physical Specifications ..................54 7.2. Sensor Specifications ..................55 © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 3 of 55...
  • Page 4: Introduction

    Using an NFC tag, the RYMASKON 200 transmits the URL to mobile devices. Last but not least, the RYMASKON 200 comes with a built-in infrared receiver for comfortable remote control. © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de...
  • Page 5: Key Features

    See Table 2 for possible order codes. Nomenclature of Order Codes Enclosure color: xx1 = black xx2 = white Button layout: Table 2: Possible Order Codes © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 5 of 55...
  • Page 6: Lcd Segments

    Cross out for drop symbol  alarm Alarm symbol  light Light bulb symbol  blinds Sun blinds symbol  clock Clock symbol © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 6 of 55...
  • Page 7 The key symbol is primarily used to show that a set point is pincode protected but it can also  be accessed via the symbol direct access registers. © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 7 of 55...
  • Page 8 The right bar graph symbols can be used to  bar_right_0 display a fan stage or valve position in automatic or manual mode.  manual_right  auto_right © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 8 of 55...
  • Page 9 Table 28 on Page 37 for set point unit_inWC configuration. unit_V unit_% unit_%RH unit_ppm Table 3: LCD Segments Overview © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 9 of 55...
  • Page 10: Quick-Start Guide

    150m for 0.5mm² or 70m for 0.25mm² to guarantee a temperature error less than 0.1% at 25°C. Figure 2: Back View RYMASKON 200 © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 10 of 55...
  • Page 11: User Interface

    <3s: cycle through display values, set points or device settings long press ~3s: switch between DISPLAY-mode and EDIT-mode long press >6s: switch to CLEANING-mode © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 11 of 55...
  • Page 12: Operating Modes

    Modbus. Please see Table 34 on Page 44 for the offset value register. Figure 4: RYMASKON 200 Operating Modes © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 12 of 55...
  • Page 13 6 seconds. After 10 seconds with no interaction the device will switch back to DISPLAY-mode automatically. Table 4: Operating Modes © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 13 of 55...
  • Page 14: Access Levels

    Per default the pincode for end user and system administrator access level is disabled (0000). Otherwise the pincode can be entered as described in Figure 5. Figure 5: Pincode Entry © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 14 of 55...
  • Page 15: Device Settings

    SI / US off – if a DOWN-button is pressed the Device Restart device will be rebooted manually Table 5: Device settings © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 15 of 55...
  • Page 16: Factory Default

    Internal Temperature Set Point set_point_1 Fan Stage set_point_2 to set_point_15 Table 6: Factory Default for RYMASKON 200 © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 16 of 55...
  • Page 17: Modbus

    Modbus address set to 1. Because each address can only be used once it has to be configured at the device settings in administration-mode. For further information please see Section 2.2. Figure 6: Modbus Network © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 17 of 55...
  • Page 18: Modbus Register Usage For Value Display

    Depending on settings in configuration registers different combinations are possible to achieve the desired result. Figure 7: Modbus Register Usage for Value Display © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 18 of 55...
  • Page 19: Modbusregister Description

    !!! The present_state register is only updated in DISPLAY- and DIRECT_ACCESS-mode! (For a list of possible modes see Table 4 on page 13) Table 7: Button States and Flags © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 19 of 55...
  • Page 20 1 is set (see Table 7 on Page 19). Table 9: IR Remote Control Command © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 20 of 55...
  • Page 21 It is advised to disable the button function at the button configuration register at address 227 (Table 24 on page 32) when used as temperature sensor input. © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de...
  • Page 22 Table 38 at Page 49 to achieve the desired result. Table 11: Display Values © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 22 of 55...
  • Page 23 This means that display_value_1 is currently displayed in DISPLAY-mode for the end user. 0x8200 – This means that set_point_0 is currently edited in administration-mode Table 13: User Interface Direct Access © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 23 of 55...
  • Page 24 8 buzzer_tone: 0x00 - 100 Hz, 0xFF - 1375 Hz (step-width = 5 Hz) Table 14: Buzzer Direct Access © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 24 of 55...
  • Page 25 The timestamp is incremented by the device but anyway it has to be set by the master at defined intervals to prevent time offsets. Table 16: System Time © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 25 of 55...
  • Page 26 !!! The statistics can be cleared by setting the MSC bit at the config_flags register at address 192 (see Table 21 on Page 29). Table 17: Modbus Statistics © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 26 of 55...
  • Page 27: Device Settings

    If set to 0000 the pincode is disabled. Possible values are 0000 (0x0000) to 9999 (0x270F). !!! Compare Table 4 on Page 15 for device settings editable via the user interface. Table 19: Pincodes © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 27 of 55...
  • Page 28 !!! Compare Table 4 on Page 15 for device settings editable via the user interface. Table 20: User Interface Settings © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 28 of 55...
  • Page 29: Configuration Registers

    Table 21: Configuration Flags © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 29 of 55...
  • Page 30 (0x00) will determine the length of the string. If a string is longer than 4 characters the secondary display will work as a ticker. Table 22: Secondary Display Direct Access String © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 30 of 55...
  • Page 31 DIRECT_ACCESS-mode !!! See Table 25 on Page 33 for example configurations. Table 23: Touch Button Configuration © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 31 of 55...
  • Page 32 DIRECT_ACCESS-mode !!! See Table 25 on Page 33 for example configurations. Table 24: External Button Configuration © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 32 of 55...
  • Page 33 EN: if set to ‘1’ the corresponding bar-graph will be updated to visualize the value of a set point with the defined set_point_index. Table 26: Bar Graph Configuration © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 33 of 55...
  • Page 34 [0x0] [0x0] [0x00] config_display_ value_11 DSSA DSEU 0x0117 unit_modbus unit semantic_meaning 0x0118 [0x0] [0x0] [0x00] config_display_ value_12 DSSA DSEU 0x0119 © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 34 of 55...
  • Page 35 Table 30 !!! See on Page 40 for example configurations of display values or set points. Table 27: Display Value Configuration © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 35 of 55...
  • Page 36 0x0154 [0x0] [0x0] [0x00] config_set_ point _10 0x0155 unit_modbus unit semantic_meaning 0x0156 [0x0] [0x0] [0x00] config_set_ point _11 0x0157 © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 36 of 55...
  • Page 37 !!! See Table 30 on Page 40 for example configurations of display values or set points. Table 28: Set Point Configuration © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 37 of 55...
  • Page 38 D A M P 0x13 Reheat (%) H E A T 0x14 Discharge Temperature D I S Table 29: Semantic Meaning © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 38 of 55...
  • Page 39 See the following example for how the display would look like © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 39 of 55...
  • Page 40 Stage 2 Manual Stage 1 Manual Stage 0 Manual Stage 0 Auto Table 30: Display Value and Set Point Example Configuration © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 40 of 55...
  • Page 41 320 to 351 (Table 28 on Page 37) the value needs to be scaled as described in Table 38 on Page 49 to achieve the desired result.. Table 31: Set Points © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 41 of 55...
  • Page 42 320 to 351 (Table 28 at Page 37) the value needs to be scaled as described in Table 38 at Page 49 to achieve the desired result.. Table 32: Set Point max. Values © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 42 of 55...
  • Page 43 320 to 351 (Table 28 at Page 37) the value needs to be scaled as described in Table 38 at Page 49 to achieve the desired result.. Table 33: Set Point min. Values © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 43 of 55...
  • Page 44 256 to 287 (Table 27 on Page 35) the value needs to be scaled the same as the corresponding display value as described in Table 38 on Page 49. Table 34: Offset Values © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 44 of 55...
  • Page 45: Model Information Registers (Read Only)

    [0x0002] [0x0002] [0x0002] [0x0002] [0x0002] [0x0008] 0x0217 default_print_external_button_0 [0x0000] 0x0218 default_print_external_button_1 [0x0000] 0x0219 default_print_external_button_2 [0x0000] 0x021A default_print_external_button_3 [0x0000] 0x021B © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 45 of 55...
  • Page 46: Device Information Registers (Read Only)

    Device Information Registers (read only) The registers shown in Table 36 are set at production and contain specific information about the device. © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 46 of 55...
  • Page 47: Nfc Registers

    NDEF URI record that is saved on the NFC tag. For further information on the NFC interface see Chapter Table 37: NFC Registers © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 47 of 55...
  • Page 48 ® RYMASKON 200-Modbus Modbus Slave User Manual © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 48 of 55...
  • Page 49: Value Scaling And Stepwidth

    !!! Whole number values are preferably displayed with the bigger digits. If an overflow occurs the number is shifted rightwards (e.g. 999 → 1000). Table 38: Value Scaling and Stepwidth © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 49 of 55...
  • Page 50: Nfc

    Since a NDEF URI record is saved at the tags memory the device will ask to open the defined URL in the browser of the NFC enabled device. © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de...
  • Page 51: Ir-Remote Control Operation

    32 (Table 9 on Page 20). Button Number Description Button Code Center Left Right Down Menu Play/Pause Table 39: Apple Remote Button Codes © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 51 of 55...
  • Page 52: Remote Control Pairing

    The pairing can be canceled by either clearing the IRCP flag or by pressing Menu and Left button for at least 6s. If the secondary display shows ‘IRUP’ (IR unpairing) shortly the pairing is suspended. © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de...
  • Page 53: Troubleshooting

    SplusS.de Tel : +49 (0) 911 / 5 19 47-0 Fax : +49 (0) 911 / 5 19 47-70 © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 53 of 55...
  • Page 54: Specifications

    Cable length for 1,0mm² 3.250 1.620 1.080 max. Power loss on cable Table 40: Cable Length and Power Loss on Cable © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 54 of 55...
  • Page 55: Sensor Specifications

    ±3 % r.H. (at +25 °C, 0... 20 % r.H. and 80...100 % r.H.) Infrared Receiver Protocol: Carrier: 38 kHz @ 950 nm Apple remote control compatible © S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |www.SplusS.de Page 55 of 55...