Parameter Table; Control Settings - S+S Regeltechnik Rymaskon 600 Operating Instructions Manual

Room control unit with colour touch screen, with bacnet or modbus connection
Table of Contents

Advertisement

Operating instructions
RYMASKON
®
600 - BACnet
RYMASKON 600 Series | Parameter Table | Last Updated: 23/03/2022 (EN)
RYMASKON
®
600 - Modbus

PARAMETER TABLE

PARAMETER TABLE
Setting Mode via unit screen
Setting mode via unit screen

CONTROL SETTINGS

Parameter name
Nominal SP
Nominal target temperature
Heating DZ COMFORT
Heating dead zone comfort
Cooling DZ COMFORT
Cooling dead zone comfort
Heating DZ ECO
Heating dead zone ECO
Cooling DZ ECO
Cooling dead zone ECO
Frost SP
Antifreeze target temperature
SP Adj. Max.
Maximum setpoint
SP Adj. Min.
Minimum setpoint
PB
IA
Heating Stages
Heating stages
Heating Stage 1 Dir.
Direction of heating stage 1
Heating Stage 2 Dir.
Direction of heating stage 2
Cooling Stages
Cooling stages
Cooling Stage 1 Dir.
Direction of cooling stage 1
Cooling Stage 2 Dir.
Direction of cooling stage 2
AUX SP
Auxiliary target temperature
AUX PB
AUX IA
AUX Dir.
Auxiliary direction
CO2 SP
CO2 setpoint
CO2 PB
S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de
Description
Nominal target temperature
NOTE:
Use this parameter to change the target
temperature via GLT. Using GLT to change
the target temperature will set the user's
manual adjustment to 0 (reset). Reset is
done only if the new setpoint deviates from
the original one. Writing the value may
need to be done twice.
Heating mode dead zone in comfort mode
(standard mode)
Cooling mode dead zone in comfort mode
(standard mode)
Heating mode dead zone in ECO mode
Cooling mode dead zone in ECO mode
Temperature where the unit switches into antifreeze mode
(antifreeze is enabled in OFF mode)
Maximum admissible upwards adjustment
of the target temperature
Maximum admissible downwards adjustment
of the target temperature
Proportional band of the temperature control circuit
Integral reset time of the temperature control circuit
0 = Disabled
Number of heating stages
Control direction of heating stage 1
Control direction of heating stage 2
Number of cooling stages
Control direction of cooling stage 1
Control direction of cooling stage 2
Target temperature for auxiliary control circuit
(see chapter "AUX control circuit")
Proportional band for auxiliary control circuit
(see chapter "AUX control circuit")
Integral reset time for auxiliary control circuit, 0 = disabled
(see chapter "AUX control circuit")
Control direction of the auxiliary control circuit
(see chapter "AUX control circuit")
Setpoint for CO2 control circuit, specified only via the bus
(see chapter "CO2 control circuit")
Proportional band for CO2 control circuit
(see chapter "CO2 control circuit")
Range
0.0...95.0°C/°F (default 21.0°C)
0.0...25.0°C/°F (default 0.5°C)
0.0...25.0°C/°F (default 0.5°C)
0.0...25.0°C/°F (default 4.0°C)
0.0...25.0°C/°F (default 4.0°C)
0.0...95.0°C/°F (default 8.0°C)
0.0...20°C/°F (default 3.0)
-20.0...0°C/°F (default -3.0)
1.0...50.0°C/°F (default 4.0)
0...1.200s (default 600s)
0 = None
1 = 1 (default)
2 = 2
0 = Reverse (100...0%, default)
1 = Direct (0...100%)
0 = Reverse (100...0%, default)
1 = Direct (0...100%)
0 = None
1 = 1 (default)
2 = 2
0 = Reverse (100...0%)
1 = Direct (0...100%, default)
0 = Reverse (100...0%)
1 = Direct (0...100%, default)
0.0...95.0°C/°F (default 21.0°C)
1.0... 50.0°C/°F (default 4.0)
0...1.200s (default 600s)
0 = Reverse (100...0%)
1 = Direct (0...100%, default)
0...5000ppm (default 1,000ppm)
10...5000ppm (default = 300ppm)