Operating instructions
RYMASKON
®
600 - BACnet
RYMASKON 600 Series | Parameter Table | Last Updated: 23/03/2022 (EN)
RYMASKON
®
600 - Modbus
INPUTS AND OUTPUTS
Parameter name
Y1
Y2
Y3
Y1 Min.
Y1 Max.
Y2 Min.
Y2 Max.
Y3 Min.
Y3 Max.
Anti-JAM
Valve protection
PWM1 Period
PWM1 duration
PWM2 Period
PWM2 duration
S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de
Description
Assignment of output capacity from control circuits
(0...100%) to the analogue output Y1 (0...10V).
Default 5 = Modulating Fan (fan)
see the following chapter:
• Analogue output modes
• Blower control relay outputs
• Temperature control relay output OPEN/CLOSE
NOTE:
The RYMASKON types 620, 630, 650 and 660
have relay outputs to control 3-speed blowers
(instead of 0...10V outputs).
Leave Y1 at Modulating Fan (default).
Assignment of output capacity from control circuits
(0...100%) to the analogue output Y2 (0...10V).
Default 1 = Htg Stage 1 (heating stage 1)
(RYMASKON 650: Default 15 = Htg Stage1 Stat)
see the following chapter:
• Analogue output modes
• Blower control relay outputs
• Temperature control relay output OPEN/CLOSE
NOTE:
Y2 is not available for RYMASKON types 640
and 660. These types require the Thermic 1/2
Mode to be configured.
Assignment of output capacity from control circuits
(0...100%) to the analogue output Y3 (0...10V).
Default 3 = Clg Stage 1 (cooling stage 1)
see the following chapter:
• Analogue output modes
• Blower control relay outputs
• Temperature control relay output OPEN/CLOSE
NOTE:
Y3 is not available for RYMASKON types
640 and 660. These types require the
Thermic 1/2 Mode to be configured.
Minimum value for Y1 output capacity
Maximum value for Y1 output capacity
Minimum value for Y2 output capacity
Maximum value for Y2 output capacity
Minimum value for Y3 output capacity
Maximum value for Y3 output capacity
If the heating/cooling valves are not activated during the
configured time, the unit will activate them briefly to
prevent jamming.
Only for RYMASKON 640/660 types
PWM duration for digital output DO1 to activate the
heating and cooling valves
(see chapter "PWM control/digital outputs")
Only for RYMASKON 640/660 types
PWM duration for digital output DO2 to activate the
heating and cooling valves
(see chapter "PWM control/digital outputs")
Range
0 = Network
1 = Htg Stage 1
2 = Htg Stage 2
3 = Clg Stage 1
4 = Clg Stage 2
5 = Modulating Fan
6 = CO2
7 = Max. VAV (Max. Clg/CO2)
8 = Max. Fan (Max. Fan/CO2)
9 = Humidification
10 = De-Humidification
11 = Lights
12 = Blind 1 Level
13 = Blind 1 Tilt
14 = Blind 2 Level
15 = Blind 2 Tilt
16 = Amber/Red
17 = Red
18 = Htg Stage1 Stat
19 = Clg Stage1 Stat
20 = Fan Stat
21 = Aux. Loop
22 = 6-Port
23 = 6-Port Reverse
0...100% (default 0%)
0...100% (default 100%)
0...100% (default 0%)
0...100% (default 100%)
0...100% (default 0%)
0...100% (default 100%)
0...14 days (default 0 = disabled)
0...120 s (Default 30s)
0 = On/Off Control
0...120 s (Default 30s)
0 = On/Off Control
39
4