Operating instructions
RYMASKON
®
600 - BACnet
RYMASKON
®
600 - Modbus

OFF MODE

Display and setting
of OFF mode
OFF ICON
(active)
TAP THE ICON
TO END THE MODE
BLIND
(toggle icon active)
LIGHT
(toggle icon inactive
→ Page 22)
S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de
MAIN SCREEN
Blind 1
8
°C
.
0
A
Room
23
°C
.5
Fig. 6
Use the bus, the digital input (e.g., PIR) or the display
to switch the controller into OFF mode.
The mode is enabled on the display via the sub screen;
the mode is disabled via the main screen.
In OFF mode, the output capacity for temperature, CO2, humidity and fan
are set to 0 %.
Depending on the configuration, the lighting in OFF mode is set to 0 %
(switched off) and the toggle icon "Lights" is disabled (see chapter "Light").
The current position of the blinds is maintained in OFF mode.
If released, the "Blind" toggle icon remains active.
If the room temperature in OFF mode drops below the antifreeze setpoint,
antifreeze is enabled (see diagram).
The display shows the snowflake icon
100 % and the fan speed to 33 %.
As soon as the temperature is 2 °C above the antifreeze setpoint,
antifreeze is switched off.
OFF MODE TEMPERATURE CONTROL
100%
Note:
In frost condition the Fan Demand
is set @ 33%
nSP = Nominal Setpoint (Default 21°C / 70°F)
0%
-
2°C /
3.6°F
fSP
fSP = Frost Setpoint (Default 8°C /46°F)
17
AUXILIARY SCREEN
Fig. 1b
, the heating stages are set to
nSP
TAP THE ICON
TO ENABLE THE MODE
+
MEASURED
TEMPERATURE