Cabinet Power System Turn-Up; Overview; Tools And Materials; Installation Of Valere Modules - ADC PG-FlexPlus PG-CAB001 Manual

Table of Contents

Advertisement

July 19, 2004
C
P
ABINET
OWER
O
VERVIEW
This section covers the turn-up of the Valere power system including installation of the rectifier modules and
procedures for verifying the integrity of the installation.
Refer to Valere Compact DC Power System Installation, Operation, and Maintenance Manual
IMPORTANT
(provided with the power system) for more details and information on operation, maintenance,
!
and troubleshooting the power system.
T
M
OOLS AND
ATERIALS
You will need the following tools and materials to install and test the Valere modules:
• Digital multimeter with an accuracy of 0.02%
• Small screwdriver (1/16-inch tip)
• Special hex key (used to open field cabinet doors)
• ESD wrist strap
I
V
NSTALLATION OF
The Valere power system is factory installed in field cabinets. Only the Valere modules are installed in the field.

Module Names

Table 13
lists the various modules and their associated Valere part numbers that are recommended for field cabinet
applications. The installation of these modules is covered in this procedure.

Preparing to Install the Modules

1. Ensure that the correct type and quantity of modules for the specific application are available.
2. Open the field cabinet door using the special hex key.
3. Locate the AC service panel in the cabinet and place all AC circuit breakers in the ON position except the
Auxiliary Generator Breaker (if equipped). A decal in the cabinet identifies the circuit breakers and their posi-
tions. If the field cabinet has a power junction box that is fed from a power pedestal, turn the AC circuit
breakers in the power pedestal feeding the cabinet in the ON position.
4. Locate the Battery Circuit Breakers and place all breakers in the OFF position.
5. Connect your ESD wrist strap to a cabinet grounding point and make sure that it is connected at all times
when handling any of the Valere molules or other plug-ins.
ADC Telecommunications, Inc.
S
T
-
YSTEM
URN
UP
M
ALERE
ODULES

Table 13. Standard Modules

Module
Rectifier (10A)
Rectifier (20A)
Rectifier (25 A)
System Controller
SCP-PGCAB001-010-01H
Valere Part Number
V500A
V1000A
V1250A
BC1000