Figure 6. Grounding Requirements For Pg-Flexplus Field Cabinet (Shown With Field Cabinet Door Removed) - ADC PG-FlexPlus PG-CAB001 Manual

Table of Contents

Advertisement

SCP-PGCAB001-010-01H
AC
Power
Panel/Junction
Box
Connect to
ground bus
Connect to lug
provided on main
cabinet ground bus
A
Route ground wire from AC power
panel directly to nearest ground rod
per NEC code Section 250-83.
Ground wire may not be spliced and
should be routed as directly as possible.
Figure 6. Grounding Requirements for PG-FlexPlus Field Cabinet
14
A
B
6 AWG (16 mm ) bare solid copper
ground wires
6 feet (1.8 m) minimum spacing
between rods
(Shown With Field Cabinet Door Removed)
2
B
Route ground wire from main cabinet
ground bus to ground rod on right side
of cabinet.
July 19, 2004
860131945-06.cdr
ADC Telecommunications, Inc.