Physical Data - Johnson Controls YORK YVAM 0350 Operation & Maintenance Manual

Centrifugal liquid chiller with r-134a refrigerant
Table of Contents

Advertisement

Physical data

Table 8: Physical data
YVAM model
Evaporator
Minimum chilled water flow rate, gpm
Maximum chilled water flow rate, gpm
Passes
Inlet/Outlet diameter, in.
Compressor
Type
Number of circuits
Number of compressors
Refrigerant type
Refrigerant charge, lb
Condenser fans
Number of fans
Fan power, 60 Hz, kW
Shipping data
(2)
Unit length, in.
Unit width, in.
Unit height, in.
Shipping weight, lb
Operating weight, lb
Note:
The minimum chilled water flow rate is for full load selections. Variable primary flow ratings
(1)
as low as 50% of the minimum are permitted. Glycol limits are higher. Contact your Johnson
Controls sales office for ratings and further information.
Shipping and operating weights are shown for the base unit. Selected options can add
(2)
weight. Contact your nearest Johnson Controls sales office for weight data.
YVAM Control Center
0350
400.0
(1)
850.0
2
6
Semi-hermetic centrifugal
1
1
R-134a
750
20
1.560
482.2
88.6
101.6
25,100
26,600
29

Advertisement

Table of Contents
loading

Table of Contents