...3 ELECTRICAL INSTALLATION

3.4 Input/Output Connections

Caution.
• Refer to SPECIFICATION SHEET for Input/Output ratings.
• Inductive loads must be suppressed or clamped to limit voltage swings
• Capacitive loads must be inrush current limited.
• Hazardous area requirements are not considered in the following pages.
Note. The connection terminal markings in the metal housed transmitter are identical to those in
the standard transmitter as shown in this section. However, the supply connection in the former
is made using a non-reversible plug (provided).
3.4.1 Frequency Outputs – Fig. 3.16
Counter/Totalisers
d.c.
supply
Forward Flow
and/or
Reverse Flow
Electromechanical
Connections
Counter/Totalisers
Forward Flow
1 2 3 4 5 6
1 2 3 4 5 6
and/or
Reverse Flow
Telemetry, Electronic
Counters etc.
Fig. 3.16 Frequency Output Connections
12
MagMaster Transmitter
F OUT A
F OUT B
PLS0V
F OUT A
F OUT B
PLS0V
3.4.2 PLC Interface – Fig. 3.17
d.c.
Fwd +
supply
Rev +
PLC
d.c. common
PLC – Common –ve
d.c.
Fwd –
supply
Rev –
PLC
PLC – Common +ve
Fig. 3.17 Frequency Output Connections
Typically
1kΩ 1W
F OUT A
F OUT B
PLS0V
F OUT A
F OUT B
PLS0V